background image

MODEL: W2XT

Space-saving Dual Output Signal Conditioners

Mini-MW Series

THERMOCOUPLE TRANSMITTER

(PC programmable)
Functions & Features
• Accepts direct input from a thermocouple and provides a
linearized process signal
• PC programmable
• Wide selection of thermocouples
• User’s temperature table can be used
• High-density mounting

89 (3.5)

 mm (inch)

124 (4.88)

29.5 (1.16)

MODEL: W2XT–[1][2][3]-[4][5]

ORDERING INFORMATION

• Code number: W2XT-[1][2][3]-[4][5]
Specify a code from below for each [1] through [5].
(e.g. W2XT-2Z1V3-M2/N/Q)
• Temperature range (e.g. 0 – 800°C)
• Output 1 range (e.g. 4 – 20 mA DC)
• Output 2 range (e.g. 1 – 5 V DC)
• Specify the specification for option code ‘Q.’
(e.g. /C01/S01)
Note: If one of the outputs should be a current range,
specify it for the Output 1 to allow a greater load.

[1] INPUT THERMOCOUPLE

1: (PR)
2: K (CA)
3: E (CRC)
4: J (IC)
5: T (CC)
6: B (RH)
7: R
8: S
9: C (WRe 5-26)
N: N

U: U
L: L
P: Platinel II
0: Specify
(Configurator software is used to change the input type and
precise range.)

[2] OUTPUT 1

Current

Z1: Range 0 – 20 mA DC

Voltage

V2: Range -10 – +10 V DC
V3: Range -5 – +5 V DC
(Configurator software is used to change output over the
described range of the selected suffix code.
For changing between suffix codes, set the Output Range
Selector on the side of unit before software adjustment.)

[3] OUTPUT 2

Same range availability as Output 1
Y: None
(Configurator software is used to change output over the
described range of the selected suffix code.
For changing between suffix codes, set the Output Range
Selector on the side of unit before software adjustment.)

[4] POWER INPUT

AC Power

M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[5] OPTIONS (multiple selections)

Standards & Approvlas (must be specified)

/N: Without CE

Other Options

blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)

/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

TERMINAL SCREW MATERIAL

/S01: Stainless steel

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание M-SYSTEM Mini-MW Series

Страница 1: ...e 10 10 V DC V3 Range 5 5 V DC Configurator software is used to change output over the described range of the selected suffix code For changing between suffix codes set the Output Range Selector on th...

Страница 2: ...0 2000 C N N 0 1000 C U U 0 300 C L L 0 500 C P Platinel II 0 1200 C OUTPUT SPECIFICATIONS DC Current Operational range 0 23 mA DC Minimum span 1 mA Offset Lower range can be any specific value withi...

Страница 3: ...20 20 20 20 20 20 20 20 20 20 20 20 20 0 to 1760 150 to 1370 170 to 1000 180 to 1200 170 to 400 400 to 1760 200 to 1760 0 to 1760 0 to 2315 130 to 1300 200 to 600 200 to 900 0 to 1395 THERMO COUPLE M...

Страница 4: ...MENSIONS unit mm inch 4 8 7 10 23 91 89 3 50 84 3 31 10 39 22 87 59 2 32 DIN RAIL 35mm wide 4 16 11 M3 SCREW 72 2 83 29 5 1 16 53 2 09 2 4 2x5 17x 20 MTG HOLE 6 24 deep 114 4 49 11 5 6 1 2 3 9 6 23 Wh...

Страница 5: ...2nd output option DIP SW DIP SW Base Socket 1 Low Drift Amplifier Burnout 2 4 Digital Computation CONFIGURATOR JACK STATUS 5 9 T C CJC SENSOR metal leg model CJM comp leadwire Specifications are subj...

Страница 6: ...s vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 30 to 90 RH in order to ensure adequate life span an...

Страница 7: ...OFF ON 1 2 3 4 Provided only for two output type CHECKING 1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Check DIP switch setting 3 Power input...

Страница 8: ...D2 LD3 indicate the transmitter s operating status by different flashing pat terns Examples are shown below LD1 LD2 LD3 A LD1 LD2 LD3 G LD1 LD2 LD3 R NORMAL OPERATION RUN MODE ERROR MODE Parameter Err...

Страница 9: ...with a copy of its original sales invoice THIS IS THE ONLY WARRANTY APPLICABLE TO M SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING ANY IMPLIED WARRANTIES OF MERCHA...

Отзывы: