To delete a card user by card. Note
users can be deleted continuously
without exiting programming mode
2 Read Card #
To delete a card user by user ID. This
option can be used when a user has
lost their card
2 User ID #
To add a card and PIN user in card and PIN mode ( 3 1 # )
To Add a card and Pin user
(The PIN is any four digits between
0000 & 9999 with the exception of
1234 which is reserved.)
Add the card as for a card user Press
* to exit from the programming mode
Then allocate the card a PIN as follows:
* Read card 1234 # PIN # PIN #
To change a PIN in card and PIN
mode (Method 1) Note that this is
done outside programming mode
so the user can undertake this
themselves
* Read Card Old PIN # New PIN #
New PIN #
To change a PIN in card and PIN
mode (Method 2) Note that this is
done outside programming mode
so the user can undertake this
themselves
* ID number # Old PIN # New PIN #
New PIN #
To delete a Card and PIN user just
delete the card
2 User ID #
To add and delete a card user in card mode ( 3 0 # )
To Add and Delete a card user
The operating is the same as adding and
deleting a card user in 3 2 #
TO DELETE ALL USERS
To delete all users. Note that this is
2 0000 # a dangerous option so use
with care
2 0000 #
TO UNLOCK THE DOOR
For a PIN
user Enter the PIN then press #
For a card User
Read card
For a card and PIN user
Read card then enter PIN #
Door settings
RELAY OUTPUT DELAY TIME
To set door relay strike time
* Master code # 4 0~99 # * 0-99 is
to set the door relay time 0-99 seconds
To disable door open detection.
(Factory default)
6 0 #
To enable door open detection
6 1 #
Changing the master code
Changing the master code
0 New code #
New code #
The master code consists of 6 to 8 digits
For security reasons we recommand changing the master code from default.
G- TECHNICAL FEATURES
> Very low power consumption (<30 mA)
> Voltage DC 12V +/-10%
> Badge reading distance 3-6 cm
> Active current < 60mA
> Stand-by current 25±5mA
> Lock load output 3A max
> Operating temperature -35°C ~ 60°C
> Degree of humidity : 10% - 90% RH
> Relay output delay time
> Possible wiring connections : electric lock, gate automation, exit button
> Backlight keys
> 100 users, supports badge, PIN, badge + PIN
> Full programming from the keypad
> Can be used as a stand alone keypad
> The keyboard can be used to remove the lost badge number, thoroughly eliminate
the hidden safety trouble
> Adjustable Door Output time, Alarm time, Door Open time
> Fast operating speed
> Lock output current short circuit protection
> Indicator light and buzzer