3 - Wiring 

 

SYSTEM POWER 

Connect 2 conductor cable (for wire size, see Table 1 
below) from TB4 at the Mini-Key unit to the 12VAC, 20 
VA transformer supplied by Sentex (or 13.5 VDC power 
supply that you provide). 
 

Do not connect the power to the system until all 
connections have been made to the system. 

 

Please Note: 

If you are using a DC power supply, the 

Mini-Key system will not trickle charge a battery, so the 
DC power must be supplied by an uninterruptible power 
supply (UPS). 

1051F7

TB4

12V AC/DC

PWR IN

2 Conductor Cable

(See Table for Wire Size and Distance)

 

Figure 5: Power Connections 

 

DISTANCE 

AC POWER WIRE SIZE 

DC POWER WIRE SIZE 

30' and under 

18 AWG 

18 AWG 

30'-75' 

18 AWG 

18 AWG 

75'-150' 

14 AWG 

18 AWG 

150'-250' 

12 AWG 

16 AWG 

250'-500' 

10 AWG 

12 AWG 

Table 1: Power Wire Distance 

 

DOOR/GATE CONTROL 

Connect the 2 conductor cable from your door strike and door strike power supply or from your gate operator to the 
relay contacts in area TB1 as follows: 
 

Door Strikes

 

 

TB1 

COM1

COM2

NO1 

NO2 

2 / 18-22 AWG

1051F12

(DC)

(DC)

AC (24v max.) or DC

POWER SOURCE

DOOR STRIKE

(DC)

(DC)

Relay 1: Connect as Shown.

Relay 2: Connect wires 

to COM2 and NO2

DC Powered Strikes

AC Powered Strikes

:

:

Use a 1N4001 Diode

or equiv.

Use a Siemens

S10K30 MOV

(Metal Oxide Varistor)

or equiv.

 

Figure 6: Normally Locked Strikes 

 

Содержание Sentex MINI-KEY

Страница 1: ...001051 Doc 6001051 Doc 6001051 Doc 6001051 Rev C Rev C Rev C Rev C MINI MINI MINI MINI KEY KEY KEY KEY INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS ...

Страница 2: ... the board s Incorrect installation also invalidates the system s warranty Take the time to read these instructions very carefully before attempting to install this system Table Of Contents SECTION PAGE NUMBER Important Notices 1 1 Basic Installation Hints and Rules 2 2 Mounting the Cabinet 3 3 Wiring 4 4 Installing Additional Features 6 Reference Main Processor Board 7 FCC Requirements 8 ...

Страница 3: ... wired to its own circuit breaker This will prevent two problems 1 Other equipment cannot introduce spikes noise surges or dips into the power circuit that will affect the Mini Key system 2 The Mini Key s operation will not be affected if any other equipment develops a short circuit across the power line DO NOT OVERLOAD THE TERMINAL BLOCKS To connect wires to a terminal block remove the head from ...

Страница 4: ...ill a 7 8 diameter hole through the bottom of the enclosure to accommodate a 1 2 conduit Be sure to securely connect the conduit to the unit Note Wires run through the bottom of the enclosure will be more prone to tampering or vandalism 3 Securely mount the unit on the wall or pedestal Mounting hardware is provided if you are using Sentex s pedestal mount post Do not put the keypad and the circuit...

Страница 5: ...e Table for Wire Size and Distance Figure 5 Power Connections DISTANCE AC POWER WIRE SIZE DC POWER WIRE SIZE 30 and under 18 AWG 18 AWG 30 75 18 AWG 18 AWG 75 150 14 AWG 18 AWG 150 250 12 AWG 16 AWG 250 500 10 AWG 12 AWG Table 1 Power Wire Distance DOOR GATE CONTROL Connect the 2 conductor cable from your door strike and door strike power supply or from your gate operator to the relay contacts in ...

Страница 6: ...nduced into the system it is strongly recommended that a 1N4001 diode be installed across the magnetic lock coil so that the cathode of the diode the end with the band is connected to the positive connection of the coil and the anode is connected to the negative connection of the coil For Dry Contact Closure Most Gate Operators 1051F13 MOST GATE OPERATORS Dry Contact Closure TB1 COM1 COM2 NO1 NO2 ...

Страница 7: ...r clock to the Mini Key system to be used in conjunction with the time clock feature This timer or clock must provide a floating contact closure a floating contact closure is a contact closure that is not grounded To install a timer or clock refer to Figure 10 TB3 2 18 24 AWG COM COM NO TZONE Timer Must have Floating Contact Closure 1051F10 Relay Contact Figure 10 Installing a Timer WARNING Any cl...

Страница 8: ...o not connect the power to the Mini Key system until all connections have been made 1 Install a remote keypad according to Figure 11 2 Connect the shields to the ground screw on the Mini Key 7 6 5 4 3 2 1 Remote Keypad Power Connections Lighted Remote Keypad Data Connections J2 2 18 AWG Ground Splice near Mini Key Unit 12V AC DC PWR IN 7 20 24 AWG EXT KYPD TB4 TB2 PINS 1 2 3 4 5 6 7 TB1 1051F9 Pow...

Страница 9: ...television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the d...

Страница 10: ...Doc 6001050 Doc 6001050 Doc 6001050 Doc 6001050 Rev C Rev C Rev C Rev C MINIKEY MINIKEY MINIKEY MINIKEY PROGRAMMING GUIDE PROGRAMMING GUIDE PROGRAMMING GUIDE PROGRAMMING GUIDE ...

Страница 11: ...TION 2 INITIAL SYSTEM SETUP 4 SECTION 3 ENTRY CODES 5 COPYRIGHT 2002 ALL RIGHTS RESERVED This document is protected by copyright and may not be copied or adapted without the prior written consent of Sentex Systems This documentation contains information proprietary to Sentex and such information may not be distributed without the prior written consent of Sentex The software and firmware included i...

Страница 12: ...it two short beeps is now ready to accept programming instructions Exit Programming Mode Press the zero two times and the pound key once 00 3 The MINIKEY system provides audio feedback to aid programming and operation The following is a list of responses and their meanings 1 short beep key was pressed 2 short beeps programming step was valid 1 long beep input was not valid 2 long beeps duplicate e...

Страница 13: ...ntry codes may be entered within a 3 minute period before the system deactivates for a period of 3 minutes The strike count will be cleared when either a valid entry code is entered or if the keypad has not had any input for 60 seconds since the last keystroke When the strike count has been reached all keypad input will be ignored including access to the programming mode Format 3 number of incorre...

Страница 14: ...information if this an option required but not implemented Entry codes are defaulted to 4 digits long and a range from 0000 9999 Valid 5 digit code range is 00000 to 99999 A ENTER AN ENTRY CODE Format 5 entry code 4 or 5 digits relay code 1 digit time clock code 1 digit Example 5 6666 1 0 sets code 6666 to activate relay 1 for the activation time regardless of clock input 5 2543 3 1 sets code 2543...

Страница 15: ......

Отзывы: