www.sentera.eu
MIW-EVS-DM-EN-000 - 14 / 03 / 2016
5 - 16
STANDARDS
■
Low Voltage Directive 2006/95/EC
■
EMC Directive 2004/108/EC: EN 61326
■
WEEE Directive 2012/19/EU
■
RoHs Directive 2011/65/EU
WIRING AND CONNECTIONS
L
Mains supply 230 VAC ± 10 % - 50 / 60 Hz
N
Neutral
PE
Earth terminal
L1
Unregulated output (230 VAC / max. 2 A)
U1, U2
Regulated output to the motor
SW
Remote / timer switch
A
Modbus RTU (RS485) signal A
/B
Modbus RTU (RS485) signal /B
+V
Supply 12 VDC / 1 mA
Ai
Analogue input:
(0—10 VDC / 0—20 mA) or (10—0 VDC / 20—0 mA)
Logic input (Timer functionality):
(min. 2,5 VDC and > 30 ms )
GND
Ground
Connections
Cable cross section: max. 2,5 mm
2
Cable gland clamping range: 3—6 mm / 5—10 mm
EVS
ELECTRONIC FAN SPEED
POWER MODULE WITH MODBUS RTU