www.sentera.eu
MIW-RDCV-EN-002 - 27 / 04 / 2017
16 - 17
Automatic (master) mode
HOLDING REGISTERS (Read / write)
Data type
Description
Data
Default
Values
40021
Master / Slave mode
unsigned int.
Selection of device operating mode
0—1
0
0 =
1
=
Slave mode
Master mode
40022
Temperature setpoint
unsigned int.
Temperature setpoint in
Master mode
0—700
200
200 =
20,0
º
C
40023
CO
2
setpoint
unsigned int.
CO
2
setpoint in
Master mode
0—2000
700
700 =
0,70 kppm
40024
Air quality setpoint
unsigned int.
Air quality setpoint in
Master mode
(Sets the content of air
pollutants in kppm)
0—2000
700
700 =
0,70 kppm
40025
Pressure setpoint
unsigned int.
Pressure setpoint in
Master mode
0—2000
100
100 =
0,10 kPa
40026
Relative humidity setpoint
unsigned int.
Relative humidity setpoint in
Master mode
0—1000
400
400 =
40,0 %
40027
Heat / Cool mode
unsigned int.
Output mode selection
0—1
0
0 =
1 =
Heat
Cool
40028
Disable / Enable PI control
unsigned int.
Disable / Enable PI control calculation for output
0—1
0
0 =
1 =
Enable
Disable
40029
Reserved, returns “0”
40030
PI control Kp value
unsigned int.
Set proportional gain for PI control
0—100
20
50 =
20 =
5,0
2,0
40031
PI control Ti value
unsigned int.
Set integrator time for PI control
0—100
20
50 =
20 =
5,0
2,0
40032
Reserved, returns “0”
40033
Display mode
unsigned int.
Display input / output value selection
0—1
0
0 =
1 =
Show sensor input value
Show controller output value
40034
Output overrule timer
unsigned int.
Set overrule timer in case output value has been changed manually
10—1440
10
10 =
1440 =
10 min
24 h
40035-
40040
Reserved, return “0”
Note
: The holding registers can be managed via the following Modbus commands: “Read Holding Registers”, “Write Single Register” or “Write Multiple Registers”.
If you want to find out more about Modbus over serial line, please visit:
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
RDCV
RESIDENTIAL HVAC
CONTROLLER