www.sentera.eu

MIW-FCMFXB-R-EN-000 - 19 / 02 / 2021

5 - 10

back to the table of contents

FCMFXB-R

INTELLIGENT CO

2

 SENSOR WITH 

BUZZER

STANDARDS

 

Low Voltage Directive 2014/35/EC 

 

 

EN 60529:1991 Degrees of protection provided by enclosures (IP Code) 
Amendment AC:1993 to EN 60529

 

 EN 60730-1:2011 Automatic electrical controls for household and similar use - 
Part 1: General requirements

 

 EMC Directive 2014/30/EC

 

 EN 60730-1:2011 Automatic electrical controls for household and similar use - 
Part 1: General requirements

 

 EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic 
standards - Immunity for residential, commercial and light industrial environments 
 EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic 
standards - Emission standard for residential, commercial and light-industrial 
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3

 

 EN 61326-1:2013 Electrical equipment for measurement, control and laboratory 
use - EMC requirements - Part 1: General requirements

 

 

EN 61326-2-3:2013 Electrical equipment for measurement, control and 
laboratory use - EMC requirements - Part 2-3: Particular requirements - Test 
configuration, operational conditions and performance criteria

 

WEEE 2012/19/EC

 

RoHs Directive 2011/65/EC

OPERATIONAL DIAGRAMS

AO1, max 

range

AO1, min 

range

60

40

100

0

rH Min range

-30

0

0 CO

2

 Min range

CO

2

 Max range

Max

Min

T Min range

T Max range

rH Max range

AO1 [%]

70

100

2.000

rH [%]

T [°C]

CO

2

 [ppm]

CAUTION

The output changes automatically depending on the highest temperature, relative 
humidity or CO

2

 values, i.e. the highest of the three output values controls the 

output. See the green line in the operational diagram above.

Содержание FCMFFB-R

Страница 1: ...FCMFXB R INTELLIGENT CO2 SENSOR WITH BUZZER Mounting and operating instructions ...

Страница 2: ...e of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODE 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION 9 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 ...

Страница 3: ...the product performance Make sure the work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always...

Страница 4: ...midity and CO2 levels Suitable for residential and commercial buildings For indoor use only TECHNICAL DATA Inset or surface mounting Bootloader for updating the firmware via Modbus RTU communication Analogue modulating output type 0 10 VDC mode min load 50 kΩ RL 50 kΩ 0 20 mA max load 500 Ω RL 500 Ω PWM open collector type PWM Frequency 1 kHz RL 50 kΩ PWM voltage level 3 3 or 12 VDC Selectable tem...

Страница 5: ...standards Emission standard for residential commercial and light industrial environments Amendments A1 2011 and AC 2012 to EN 61000 6 3 EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements EN 61326 2 3 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 2 3 Particular requirements Test co...

Страница 6: ...wer supply and for analogue output Connecting both grounds together might result in incorrect measurements Minimum four wires are required to connect F type sensors The G version is intended for 3 wire connection and features a common ground This means that the ground of the analogue output is internally connected to the ground of the power supply For this reason F and G types of the product canno...

Страница 7: ...nting dimensions shown in Fig 2 and Fig 3 Fig 2 Mounting dimensions inset mounting Fig 3 Mounting position 38 15 58 82 82 89 76 58 58 52 Correct Incorrect Position at min 1 5 m from the floor 5 Put back the frame cover of the enclosure and secure it with the screws 6 Switch on the power supply 7 Customise the factory settings to the desired ones via the 3SModbus software or the Sensistant configur...

Страница 8: ...software or the Sensistant configurator For the default factory settings see the Modbus register map NOTE Mount the unit so that the terminal block and connections are at the lower side NOTE For the complete Modbus register data refer to the product Modbus Register Map which is a separate document attached to the article code on the website and contains the registers list Products with earlier fir...

Страница 9: ...on the measured value temperature relative humidity or CO2 is between the minimum and maximum alert range values Fig 6 1 In this case the audible alarm is OFF 2 When the yellow LED is on the measured value temperature relative humidity or CO2 is in the alert range Fig 6 2 In this case the audible alarm is ON 3 When the red LED is on the measured value temperature relative humidity or CO2 is below ...

Страница 10: ...er switching on the power supply one of the LEDs lights up according to the status of the measured variable If this is not the case check the connections TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publ...

Отзывы: