3.2. Network topology and channel length 

The maximum wiring length for channel segment depends on the network topology and cable type. 
The

 

maximum wire length values for channel could be increased by using the TP/FT-10 repeaters to connect 

two channel segments. 

 

Table 2: 

Free Topology

  

 

Recommended cable type 

Maximum wire length 

with no repeaters in meters 

Maximum device-to-device 

distance in meters 

TIA 568A Category 5 cable 

450 

250 

J-Y(St)Y 2x2x0.8 cable 

500 

320 

Level IV cable 

500 

400 

Belden 8471 or equivalent cable 

500 

400 

Belden 85102 or equivalent cable 

500 

500 

 
Table 3: 

Doubly-terminated Bus Topology

 

 

Recommended cable type 

Maximum wire length 

with no repeaters in meters 

Maximum stub length 

in meters 

TIA 568A Category 5 cable 

900 

J-Y(St)Y 2x2x0.8 cable 

900 

Level IV cable 

1400 

Belden 8471 or equivalent cable 

2700 

Belden 85102 or equivalent cable 

2700 

 

Use only the dedicated terminators - one terminator in free topology and two terminators on both ends 
of network channel in bus topology. In case of any question, please contact technical support

3.3. Integration in the LonWorks network 

It is recommended that the process of integration of the LonWorks option module (setting the logical address 
and state of device as Configured and Online or defining the bindings between the network variables of 
another LonWorks devices) was performed by trained personnel, using dedicated tools, such as Echelon 
OpenLNS Commissioning Tool software or other LonWorks platform based on Echelon LonWorks Network 
Services (OpenLNS) or fully compliant the ISO/IEC 14908 (EN14908-1, CEA-709) standards. 
 
The integration of the LonWorks module should be performed using the eXternal Interface File (XIF File) 
which describe the LonMark device interface of module (like network variables used by the option module)  
in format supported by the network integration tool. The XIF File and the LonMark Resource Files used to 
integrate the option module in the LonWorks network are available to download from 

sensus.com

 website. 

Содержание LonWorks TP/FT-10

Страница 1: ... between Network and Option Module 277 VRMS 0 60 Hz Number of LonWorks Devices per Segment Up to 64 Power down Network Protection High impedance when module is unpowered 1 3 Environmental requirements Operating Temperature ambient 5 to 50 C Storage Temperature 10 to 65 C Operating and Storage Humidity 25 to 90 RH 50 C non condensing 2 Safety instructions The installation electrical connection and ...

Страница 2: ...onal pulse input or output 51 2nd additional pulse input or output In Out2 Volume output on TEST mode 52 GND for 1st additional pulse input or output 53 1st additional pulse input or output In Out1 Energy output on TEST mode LonWorks module clamp no Description 60 12 24 V AC DC SELV power supply 61 12 24 V AC DC SELV power supply 96 LonWorks TP FT 10 channel interface 97 LonWorks TP FT 10 channel ...

Страница 3: ... 2700 3 Use only the dedicated terminators one terminator in free topology and two terminators on both ends of network channel in bus topology In case of any question please contact technical support 3 3 Integration in the LonWorks network It is recommended that the process of integration of the LonWorks option module setting the logical address and state of device as Configured and Online or defi...

Страница 4: ... to reset the Update Rate parameter to default value 10 minutes 3 5 Firmware Update The option module firmware update can be done by user Downloading the firmware to device is performed by dedicated software run on Microsoft Windows operating system or by using the option Load application image and attach an Image file path to the Echelon OpenLNS Commissioning Tool during the module commissioning ...

Страница 5: ...flow_f IEEE754 l s Flow Rate Fixed nvoFlowRateP SNVT_flow_p Int16 m3 h Forward temperature nvoForwardTemp SNVT_reg_val_ts Int32 C Forward temperature Float nvoForwardTempF SNVT_temp_f IEEE754 C Forward temperature Fixed nvoForwardTempP SNVT_temp_p Int16 C Return temperature nvoReturnTemp SNVT_reg_val_ts Int32 C Return temperature Float nvoReturnTempF SNVT_temp_f IEEE754 C Return temperature Fixed ...

Страница 6: ...rror 0000 Hardware status flag Er02 bit2 Hardware status flag Er02 8000 Hardware status flag Er03 bit3 Hardware status flag Er03 8000 End of battery life time bit4 End of battery life time 1000 Hardware status flag Er05 bit5 Hardware status flag Er05 0008 Hardware status flag Er06 bit6 Hardware status flag Er06 0008 Flow sensor is empty Air in the ultrasonic flow sensor bit10 Flow sensor is empty ...

Страница 7: ...nd left side Put the option module into the designated contact sockets The contact pins must not be bent Mount the fixing screws Install the additional battery into the second battery holder and plug in the connector to the second battery connector Route the connecting cable through an available cable fitting and make a pull relief Then connect the wires to the respective terminals Close the lid a...

Страница 8: ...All trademarks are the property of their respective owners Edition 001 1503 030 0002 01A Subject to changes without notice Sensus GmbH Ludwigshafen Industriestraße 16 D 67063 Ludwigshafen Phone 49 0 621 6904 1000 Certified according to ISO 9001 Fax 49 0 621 6904 1409 Quality Management System Quality Austria Reg no 3496 0 E Mail info int xyleminc com www sensus com ...

Отзывы: