User Manual
LonWorks TP/FT-10
Option module for PolluStat
M H 6144 INT, page 2
3. Installation the option module in the LonWorks network
3.1. Connection diagram
Picture 2: electrical connection diagram
Table 1:
Number markers on the screw connector clamps
Calculator:
clamp no.
description
5
temperature sensor T1 (warmer pipe/supply pipe)
6
temperature sensor T1 (warmer pipe/supply pipe)
7
temperature sensor T2 (colder pipe/return pipe)
8
temperature sensor T2 (colder pipe/return pipe)
50 GND
for
2
nd
additional pulse input or output
51 2
nd
additional pulse input or output (In / Out2) (Volume output on TEST mode)
52 GND
for
1
st
additional pulse input or output
53 1
st
additional pulse input or output (In / Out1) (Energy output on TEST mode)
LonWorks module:
clamp no.
Description
60
12-24 V AC/DC SELV power supply
61
12-24 V AC/DC SELV power supply
96 LonWorks
TP/FT-10
channel
interface
97 LonWorks
TP/FT-10
channel
interface
The pairs of clamps 60, 61 (for connect SELV power supply) and 96, 97 (for connect to LonWorks network
based on TP/FT-10 channel) are polarity insensitive.
Battery 3.6V
LonWorks TP/
F
T
-10
commun
icati
o
n
modu
le
Additional
Battery 3.6V
to SELV power supply
to LonWorks network (TP/FT-10 channel)
T1
T2