1.  Use of the option module 

The LonWorks TP/FT-10 option module is used to connect the PolluStat heat meter to LonWorks network 
using TP/FT-10 channel. 

 

Picture 1: LonWorks module

 

 
The module is based on LonWorks 2.0 technology on Echelon FT 5000 Smart Transceiver chip. No credits 
charge in OpenLNS CT and LonMaker/LNS Turbo Edition applications during commissioning the modules.

 

The module is compliant to ISO/IEC 14908-1 (EN14908-1, CEA-709.1) and ISO/IEC 14908-2 (EN14908-2, 
CEA-709.3) standard. 

1.1. Power supply 

The LonWorks module should be powered by AC or DC (polarity insensitive) SELV power supply only. 
SELV 

Power 

Supply 

Voltage 

    12-24 

AC/DC 

±10% 

Power 

Consumption 

     max. 

0.1 

Typical 

Supply 

Current 

     6 

mA 

@12 

DC 

1.2. Communication interface 

Connection to LonWorks network is realized by using Free Topology Twisted Pair TP/FT-10 interface. 
Data 

Communications 

Type 

    Differential 

Manchester 

encoding 

Network 

Polarity      Polarity 

insensitive 

Transmission 

Speed 

     78 

kilobits 

per 

second 

Galvanic Isolation between Network and Option Module  

277 V

RMS

 (0-60 Hz) 

Number of LonWorks Devices per Segment 

 

 

Up to 64 

Power-down Network Protection 

 

 

 

High impedance when module is unpowered 

1.3. Environmental requirements 

Operating 

Temperature 

(ambient) 

   +5 

to 

+50°C 

Storage 

Temperature 

     -10 

to 

+65°C 

Operating and Storage Humidity 

 

 

 

25 to 90 % RH @50°C, non-condensing 

2. Safety 

instructions 

 

The installation, electrical connection and commissioning the module should be made 
by qualified specialists only. 

  The LonWorks option modules may only be used for the PolluStat meter, otherwise 

the modules or the heat meter could be damaged. 

  The included lithium battery and the meter battery must not be recharged, 

 

short-circuited, put in contact with water or exposed to temperatures of more than 80°C. 

  Batteries and module waste may only be disposed at suitable collection centers 

for professional waste disposal. 

  The communication modules are delivered in the form of circuit board. Is highly 

recommended that normal static precautions be taken in handling and assembly of this 
module to prevent damage and/or degradation which may be induced by ESD. Failure 
to observe proper handling and installation procedures can cause damage. ESD 
damage can range from subtle performance degradation to complete device failure.

 

Содержание LonWorks TP/FT-10

Страница 1: ... between Network and Option Module 277 VRMS 0 60 Hz Number of LonWorks Devices per Segment Up to 64 Power down Network Protection High impedance when module is unpowered 1 3 Environmental requirements Operating Temperature ambient 5 to 50 C Storage Temperature 10 to 65 C Operating and Storage Humidity 25 to 90 RH 50 C non condensing 2 Safety instructions The installation electrical connection and ...

Страница 2: ...onal pulse input or output 51 2nd additional pulse input or output In Out2 Volume output on TEST mode 52 GND for 1st additional pulse input or output 53 1st additional pulse input or output In Out1 Energy output on TEST mode LonWorks module clamp no Description 60 12 24 V AC DC SELV power supply 61 12 24 V AC DC SELV power supply 96 LonWorks TP FT 10 channel interface 97 LonWorks TP FT 10 channel ...

Страница 3: ... 2700 3 Use only the dedicated terminators one terminator in free topology and two terminators on both ends of network channel in bus topology In case of any question please contact technical support 3 3 Integration in the LonWorks network It is recommended that the process of integration of the LonWorks option module setting the logical address and state of device as Configured and Online or defi...

Страница 4: ... to reset the Update Rate parameter to default value 10 minutes 3 5 Firmware Update The option module firmware update can be done by user Downloading the firmware to device is performed by dedicated software run on Microsoft Windows operating system or by using the option Load application image and attach an Image file path to the Echelon OpenLNS Commissioning Tool during the module commissioning ...

Страница 5: ...flow_f IEEE754 l s Flow Rate Fixed nvoFlowRateP SNVT_flow_p Int16 m3 h Forward temperature nvoForwardTemp SNVT_reg_val_ts Int32 C Forward temperature Float nvoForwardTempF SNVT_temp_f IEEE754 C Forward temperature Fixed nvoForwardTempP SNVT_temp_p Int16 C Return temperature nvoReturnTemp SNVT_reg_val_ts Int32 C Return temperature Float nvoReturnTempF SNVT_temp_f IEEE754 C Return temperature Fixed ...

Страница 6: ...rror 0000 Hardware status flag Er02 bit2 Hardware status flag Er02 8000 Hardware status flag Er03 bit3 Hardware status flag Er03 8000 End of battery life time bit4 End of battery life time 1000 Hardware status flag Er05 bit5 Hardware status flag Er05 0008 Hardware status flag Er06 bit6 Hardware status flag Er06 0008 Flow sensor is empty Air in the ultrasonic flow sensor bit10 Flow sensor is empty ...

Страница 7: ...nd left side Put the option module into the designated contact sockets The contact pins must not be bent Mount the fixing screws Install the additional battery into the second battery holder and plug in the connector to the second battery connector Route the connecting cable through an available cable fitting and make a pull relief Then connect the wires to the respective terminals Close the lid a...

Страница 8: ...All trademarks are the property of their respective owners Edition 001 1503 030 0002 01A Subject to changes without notice Sensus GmbH Ludwigshafen Industriestraße 16 D 67063 Ludwigshafen Phone 49 0 621 6904 1000 Certified according to ISO 9001 Fax 49 0 621 6904 1409 Quality Management System Quality Austria Reg no 3496 0 E Mail info int xyleminc com www sensus com ...

Отзывы: