User Manual
LonWorks TP/FT-10
Option module for PolluStat
M H 6144 INT, page 1
1. Use of the option module
The LonWorks TP/FT-10 option module is used to connect the PolluStat heat meter to LonWorks network
using TP/FT-10 channel.
Picture 1: LonWorks module
The module is based on LonWorks 2.0 technology on Echelon FT 5000 Smart Transceiver chip. No credits
charge in OpenLNS CT and LonMaker/LNS Turbo Edition applications during commissioning the modules.
The module is compliant to ISO/IEC 14908-1 (EN14908-1, CEA-709.1) and ISO/IEC 14908-2 (EN14908-2,
CEA-709.3) standard.
1.1. Power supply
The LonWorks module should be powered by AC or DC (polarity insensitive) SELV power supply only.
SELV
Power
Supply
Voltage
12-24
V
AC/DC
±10%
Power
Consumption
max.
0.1
W
Typical
Supply
Current
6
mA
@12
V
DC
1.2. Communication interface
Connection to LonWorks network is realized by using Free Topology Twisted Pair TP/FT-10 interface.
Data
Communications
Type
Differential
Manchester
encoding
Network
Polarity Polarity
insensitive
Transmission
Speed
78
kilobits
per
second
Galvanic Isolation between Network and Option Module
277 V
RMS
(0-60 Hz)
Number of LonWorks Devices per Segment
Up to 64
Power-down Network Protection
High impedance when module is unpowered
1.3. Environmental requirements
Operating
Temperature
(ambient)
+5
to
+50°C
Storage
Temperature
-10
to
+65°C
Operating and Storage Humidity
25 to 90 % RH @50°C, non-condensing
2. Safety
instructions
The installation, electrical connection and commissioning the module should be made
by qualified specialists only.
The LonWorks option modules may only be used for the PolluStat meter, otherwise
the modules or the heat meter could be damaged.
The included lithium battery and the meter battery must not be recharged,
short-circuited, put in contact with water or exposed to temperatures of more than 80°C.
Batteries and module waste may only be disposed at suitable collection centers
for professional waste disposal.
The communication modules are delivered in the form of circuit board. Is highly
recommended that normal static precautions be taken in handling and assembly of this
module to prevent damage and/or degradation which may be induced by ESD. Failure
to observe proper handling and installation procedures can cause damage. ESD
damage can range from subtle performance degradation to complete device failure.