Sensus FM-1D/K Скачать руководство пользователя страница 3

the lower status LED blinks the last 4 digits can be set.
The setting is identical as described in point 1. The posi-
tion of the decimal point depends on the output pulse
value ( see point 4)

3.

Pulser 

The setting of the pulse value of the sensor in litre per
pulse. In this example with 1 litre per pulse the display is
to be set to ”0001.”. The possible input pulse range is
0.001 ... 9999. litres/pulse. After the pulse value pro-
gramm the signal mode suitable for the connected pulser.
InPu= Opto OD 01-04 without evaluation of the direction
signal
InPb= Opto OD 01-04 with evaluation of the direction sig-
nal

InPr= Opto OD 01-04 without direction signal

4.

Pulse output

For example to set 1 pulse per m

3

, the display must indi-

cate ”0001.”. The setting is identical as described in
point 1. The possible output pulse value is 0.001 ...
9999.m

3

. Note ! The output pulse value has to be > to the

input pulse value. At max. flowrate the output pulse rate
must not exceed 1 Hz.

5.

Current output

The actual current output range will be indicated at the
display. With the (+) or (-)-button it can be toggled
between 0...20mA and 4...20mA. Pressing the SELECT
button saves the setting.

6.

Damping 

The damping determines the response time of the cur-
rent output and the flowrate indication.
If there are no special requirements for the response
time please set damping value ”0004”.
Setting 1 - no damping  Setting 14 - max. damping

*) from serial no. 105.000

5. Protection

The FM-1D/K can be protected against unintentional
changes to the setting. In the protect-mode all settings
and measuring values can be displayed. Changing the
values is not possible.

Simultaneously by pressing (+) and (-)-buttons and the
SELECT-button, the present mode will be displayed.

display ”LOC 6”

- device in programming mode,

display ”LOC 8”

- device protected.

With the (+) or (-)-buttons modes can be toggled
between ”LOC 6” and ”LOC 8”. Pressing the SELECT
button saves the setting.

6. Test mode

In the test-mode the digital and ana-
logue output of the FM-1D/K can be

checked on the integral counter and flowrate indicator,
without having a pulser connected to the pulse input.

First the firmware revision will be indicated.

By pressing the  (+) or (-)-buttons the test mode starts:

The current output toggles, as indicated on the display,
in a 30 second interval between 0(4) und 20 mA. The
flowrate indicator should alternate between ”0” and full
scale.

At the pulse output terminals a pulse will be generated
every 60 seconds. These pulses will be indicated on
the pulse counter.

Pressing the SELECT-button leaves the test mode and
changes into the standard mode.

Test

I in mA

t in sec.

Pulse

Pulse

30

60

90

20

4

120

Содержание FM-1D/K

Страница 1: ... 9 Trouble shooting 10 Replacing fuses 1 Description FM 1D K is a µP controlled frequency converter with display It converts pulses into proportional cur rent for flowrate display Input from the pulsers are converted to Standardized current Pulse totalization LED display 2 Mounting Snap action on 35mm top hat rail acc to EN 50022 remove from top hat rail Wall mounting with two screws M5 M4 50 60 8...

Страница 2: ...ed digit will flash With the and button the settings can be changed To activate the second placed digit the SELECT but ton must be pressed 3 Save To save the chosen settings the SELECT but ton must be pressed after changing the last right hand digit The settings will not be lost after a power failure Setting example Water meter WPD DN 80 Pulser Opto OD 01 1 imp 1 Ltr Current output 0 20 mA Max flo...

Страница 3: ...he cur rent output and the flowrate indication If there are no special requirements for the response time please set damping value 0004 Setting 1 no damping Setting 14 max damping from serial no 105 000 5 Protection The FM 1D K can be protected against unintentional changes to the setting In the protect mode all settings and measuring values can be displayed Changing the values is not possible Sim...

Страница 4: ...emedy 9 Trouble Shooting Status lamps and LED dis play not work ing No current out put but internal display indi cates flowrate No power supply Error in the current out put circuit Check current output using the test mode Check connected indica tor Check external totalizer and its power supply No pulse output but the internal display counts the volume Error in the pulse output circuit Check pulse ...

Страница 5: ...s Exchange pulser Opto or inductive Use additional contact protection relay Indication InPe Pulse error Change pulse signal InPb or InPu for Opto OD InPr for Reed RD 10 Replacing fuses Disconnect the power from the FM 1 D K Remove the 4 screws from the front plate Remove front plate with boards from the housing Remove the board with the blown fuse from the front plate Open the holding device check...

Отзывы: