3. Connection

Note:

• max cable cross section is 2.5 mm

2

• check power supply voltage before using

• with 24 VDC operation, the polarity is irrelevant 

• Technical Data please see leaflet L S 5100 GB

 

Safety information

When making the electrical connections, it is
essential to disconnect the FM-1 D/K from the
power supply.

The connection of the FM-1D/K is only allowed by
a specialist in accordance to the common safety
standards.

Connection of 3-wire-sensors

4. Calibration by hand

+ Sensor -

U+

L

N

PE

24 VAC/DC

12345678

+

-

FM-1D/K

select

   

 

   

   

       

   

       

       

 

 

   

   

   

   

   

 

   

 

 

+

-

Status LEDs

select key

change keys

LED display

Calibration

After connecting the FM-1 D/K needs to be calibrated:

1. Select 

With the SELECT- button the programming 

parameters can be chosen. The status LED indicates
the actual selection.

2. Change

By pressing either the (+) or (-) button the 

status LED and the first placed digit will flash. With 
the (+) and (-) button the settings can be changed.
To activate the second placed digit the SELECT-but
ton must be pressed.

3. Save 

To save the chosen settings the SELECT-but

ton must be pressed after changing the last right 
hand digit.
The settings will not be lost after a power failure.

Setting example

Water meter

WPD DN 80

Pulser

Opto OD 01  (1 imp = 1 Ltr.)

Current output

0 ... 20 mA 

Max. flowrate

0 ... 100 m

3

/h

Pulse output

1 Imp. = 1 m

3

1.

Flowrate range 

After switching on, the display indicates ”0000.”.
Pressing either the (+) or (-)-button the FM-1 D/K
changes to the programming mode. The left digit of the
display will flash. Set the digit ”0” with the (+) or (-)-but-
ton. Pressing the  SELECT-button changes to the sec-
ond digit. As described set the 2.,3.,4. digit and the deci-
mal point.The display should indicate  ”0100.”. The pos-
sible flowrate range is 0.001 ... 9999. m

3

/h

2.

Counter reading

The FM-1 D/K counter reading can be set to match the
counter reading of the water meter. When the upper sta-
tus LED blinks the first 4 digits can be set and when

Содержание FM-1D/K

Страница 1: ... 9 Trouble shooting 10 Replacing fuses 1 Description FM 1D K is a µP controlled frequency converter with display It converts pulses into proportional cur rent for flowrate display Input from the pulsers are converted to Standardized current Pulse totalization LED display 2 Mounting Snap action on 35mm top hat rail acc to EN 50022 remove from top hat rail Wall mounting with two screws M5 M4 50 60 8...

Страница 2: ...ed digit will flash With the and button the settings can be changed To activate the second placed digit the SELECT but ton must be pressed 3 Save To save the chosen settings the SELECT but ton must be pressed after changing the last right hand digit The settings will not be lost after a power failure Setting example Water meter WPD DN 80 Pulser Opto OD 01 1 imp 1 Ltr Current output 0 20 mA Max flo...

Страница 3: ...he cur rent output and the flowrate indication If there are no special requirements for the response time please set damping value 0004 Setting 1 no damping Setting 14 max damping from serial no 105 000 5 Protection The FM 1D K can be protected against unintentional changes to the setting In the protect mode all settings and measuring values can be displayed Changing the values is not possible Sim...

Страница 4: ...emedy 9 Trouble Shooting Status lamps and LED dis play not work ing No current out put but internal display indi cates flowrate No power supply Error in the current out put circuit Check current output using the test mode Check connected indica tor Check external totalizer and its power supply No pulse output but the internal display counts the volume Error in the pulse output circuit Check pulse ...

Страница 5: ...s Exchange pulser Opto or inductive Use additional contact protection relay Indication InPe Pulse error Change pulse signal InPb or InPu for Opto OD InPr for Reed RD 10 Replacing fuses Disconnect the power from the FM 1 D K Remove the 4 screws from the front plate Remove front plate with boards from the housing Remove the board with the blown fuse from the front plate Open the holding device check...