Operating Instructions
Frequency Converter FM-1D/K

Digital-analogue-converter
and flow rate indicator for water meters

Contents

1.

Description

2.

Mounting

3.

Connection

4.

Calibration by hand

5.

Protection

6.

Test mode

7.

Operation

8.

Lightning protection

9.

Trouble shooting

10.

Replacing fuses

1. Description

FM-1D/K is a µP-controlled frequency
converter with display.

It converts pulses into proportional cur-
rent for flowrate display.

Input from the pulsers are converted to:

• Standardized current
• Pulse totalization
• LED display

2. Mounting

Snap action on
35mm top hat
rail acc. to EN
50022

remove from
top hat rail

Wall mounting
with two screws

M5

M4

50

60

85

+ Sensor -

U+

N

PE

24 VAC/DC

12345678

+

-

+

-

FM-1D/K

select

   

  

  

   

   

Содержание FM-1D/K

Страница 1: ... 9 Trouble shooting 10 Replacing fuses 1 Description FM 1D K is a µP controlled frequency converter with display It converts pulses into proportional cur rent for flowrate display Input from the pulsers are converted to Standardized current Pulse totalization LED display 2 Mounting Snap action on 35mm top hat rail acc to EN 50022 remove from top hat rail Wall mounting with two screws M5 M4 50 60 8...

Страница 2: ...ed digit will flash With the and button the settings can be changed To activate the second placed digit the SELECT but ton must be pressed 3 Save To save the chosen settings the SELECT but ton must be pressed after changing the last right hand digit The settings will not be lost after a power failure Setting example Water meter WPD DN 80 Pulser Opto OD 01 1 imp 1 Ltr Current output 0 20 mA Max flo...

Страница 3: ...he cur rent output and the flowrate indication If there are no special requirements for the response time please set damping value 0004 Setting 1 no damping Setting 14 max damping from serial no 105 000 5 Protection The FM 1D K can be protected against unintentional changes to the setting In the protect mode all settings and measuring values can be displayed Changing the values is not possible Sim...

Страница 4: ...emedy 9 Trouble Shooting Status lamps and LED dis play not work ing No current out put but internal display indi cates flowrate No power supply Error in the current out put circuit Check current output using the test mode Check connected indica tor Check external totalizer and its power supply No pulse output but the internal display counts the volume Error in the pulse output circuit Check pulse ...

Страница 5: ...s Exchange pulser Opto or inductive Use additional contact protection relay Indication InPe Pulse error Change pulse signal InPb or InPu for Opto OD InPr for Reed RD 10 Replacing fuses Disconnect the power from the FM 1 D K Remove the 4 screws from the front plate Remove front plate with boards from the housing Remove the board with the blown fuse from the front plate Open the holding device check...

Отзывы: