SENSORWORX SWX-950 Скачать руководство пользователя страница 7

CONFIGURATION SETTINGS 

(

CONT.)

FUNCTION #4 TURN ON / PARTIAL ON LEVEL)

The level the dimming output is set to upon initially turning on (requires unit be in a Partial 
On operating mode).

SETTING #

VALUES

NOTES

2

100%

3

Last User Level (default)

Invalid if Operational Mode set to Partial Off.

4

~30%

Actual voltage value is calculated as the % of 
voltage range between high and low trim levels.
Light output at each voltage level depends on 
driver/ballast and luminaire.

5

~40%*                         

6

~50%

7

~60%

8

~70%

9

~80%

FUNCTION #5 TURN OFF SCHEME 

The actions of the power pack’s dimming output and relay when an unoccupied signal or 
an off switch press is received.

SETTING #

VALUES

NOTES

2

Drop to Off*

Dimming output drops to low trim and relay opens
(*default)

3

Fade to Off

Dimming output fades to low trim and relay opens

4

Fade to 0V

Dimming output fades to 0 volts (e.g. below a connected 
driver’s electronic off level). Relay remains closed.

5

Fade to Low Trim

Dimming output fades down to low trim level. Relay remains 
closed.

6

Drop to Low Trim

Dimming output drops down to low trim level. Relay remains 
closed.

7

Drop to OV

Dimming output drops to 0 volts (e.g. below a connected 
driver’s electronic off level). Relay remains closed.

FUNCTION #6 HIGH TRIM 

The voltage of the dimming output at the full bright level (step). 

SETTING #

VALUES

NOTES

2

10 VDC (100%) *                  *default

Exact light output % at each voltage 
level depends on driver/ballast and 
luminaire.

3

9 VDC (90%)

4

8 VDC (80%)

5

7 VDC (70%)

6

6 VDC (60%)

7

5 VDC (50%)

FUNCTION #7 LOW TRIM 

The voltage to which the dimming output will drop when the unit is in the off state. This 
setting is only active when the unit’s 

Turn Off Scheme

 is set to Dim to Low Trim.

SETTING #

VALUES

NOTES

2

0 VDC

Exact light output % at each voltage 
level depends on driver/ballast and 
luminaire.

3

1 VDC (10%) 

4

2 VDC (20%)

5

3 VDC (30%)*                       *default

6

4 VDC (40%)

7

5 VDC (50%)

FUNCTION #9 FADE OFF TIME 

SETTING #

VALUES

NOTES

2

0.75 Sec

3

1.5 Sec*

*default

4

3 Sec

5

5 Sec

6

15 Sec

FUNCTION #10 FADE ON TIME

SETTING #

VALUES

NOTES

2

0.75 Sec

3

1.5 Sec*

*default

4

3 Sec

5

5 Sec

6

15 Sec

DETAILED DIMMING CONFIGURATION

Several dimming parameters (listed in the tables below) can be adjusted. A step-by-step programming procedure is listed below the tables.

CHANGING A DETAILED DIMMING CONFIGURATION SETTING
1

  From the below tables of detailed dimming functions, note the number (#) of the function to be modified. For example, the 

TURN ON /PARTIAL ON LEVEL 

function is #4.

2

  To enter programming mode, press and release the unit’s button the number of times of the chosen function. For example, press the button 4 times to access the 

TURN ON /PARTIAL 

ON LEVEL

.

3

  The LED will flash back the setting number of the current value as it appears in each function’s detailed table below. For example, the default 

TURN ON /PARTIAL ON LEVEL 

is 

setting #3, Last User Level). Continue to the next step before the current setting is blinked back 3x).

4

  To change the setting number, interrupt the blink back and press and release the button the number of times equal to the new setting #. For example, 3 times (for 3V, ~30%).

5

  The LED will flash back the new setting number as confirmation and will be saved after three confirmations. After the third confirmation sequence, a successful save is indicated by a 

two sets of rapid White flashes. If the Blue LED rapid flashes twice, save was unsuccessful and process should be started over.

Содержание SWX-950

Страница 1: ...p to 50 Remote Devices à Switches Up to 20A Line Voltage Loads à Electronically Timed Switching Ensures Long Relay Life à Integrated Test Programming Button à Configurable Time Delays and Operational Modes e g Occupancy Vacancy à Optional 0 10V Dimming Output for Partial On Partial Off Operation à Optional Low Voltage Sensor Wall Station Wired Connectivity à Plenum Rated UL 2043 OVERVIEW SENSORWOR...

Страница 2: ...ple as Class 1 circuits 2 Suitable for plenum use 3 Risk of Electric Shock More than one disconnect switch may be required to de engergize the equipment before servicing WARNING TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING BLU YEL BLK BLU WHT N 277V 120V OR CAP UNUSED BLACK OR YELLOW WIRE LOAD 120V 277V SWX 950 WIRELESS POWER PACK BLK COMMON 0 10V DIMMING OUTPUT VIO BLU YEL BLK BLU WHT N 27...

Страница 3: ...WER REQUIRED 15 30mA 0 0 0 0 30mA 90mA 15 30mA 0 0 1 55mA 85mA 90mA 0 0 9 90mA 0 0 90mA 90mA 7 14mA 8 80mA 0 0 94mA 90mA POWER PACK CAPACITY or low voltage wall switches EXAMPLE COMBINATIONS COMPATIBLE WIRELESS DEVICES MODEL DESCRIPTION WIRELESS TYPE POWER TYPE SWX 201 B Small Motion 360 Sensor PIR Transmit Battery SWX 401 B Wide View Sensor PIR Transmit Battery SWX 402 B Long Range Hallway Sensor...

Страница 4: ...he full bright level when occupied and dropped to the 50 level is configurable during unoccupied periods à Partial On operation can be achieved by the SWX 950 D2 unit In this configuration 0 10V lighting is turned on to a configurable Partial On Level when triggered from an occupancy sensor or switch Lighting can then be adjusted to any level via a wirelessly linked SWX 854 B remote dimmer Alterna...

Страница 5: ...ccupancy Lights will be switched off once all linked sensors have continously reported unoccupied for the duration of the time delay à If a power pack does not receive a heartbeat transmission from a linked sensor for 2 minutes it will consider itself occupied SWX 950 series power packs have many configurable functions depending on the specific model All functions setting values can be accessed an...

Страница 6: ...sequence of operation choices CHANGING THE OPERATIONAL MODE 1 Read through the above list and note the number of the desired setting e g 2 Automatic On Occupancy Mode 2 Press and release the unit s pushbutton 3 times then wait 2 seconds The White LED will blink back the number of the current setting repeats 3x before exiting 3 Interrupt blink back by pressing the button the number times equal to t...

Страница 7: ... setting is only active when the unit s Turn Off Scheme is set to Dim to Low Trim SETTING VALUES NOTES 2 0 VDC Exact light output at each voltage level depends on driver ballast and luminaire 3 1 VDC 10 4 2 VDC 20 5 3 VDC 30 default 6 4 VDC 40 7 5 VDC 50 FUNCTION 9 FADE OFF TIME SETTING VALUES NOTES 2 0 75 Sec 3 1 5 Sec default 4 3 Sec 5 5 Sec 6 15 Sec FUNCTION 10 FADE ON TIME SETTING VALUES NOTES...

Страница 8: ...re requirements this device must be installed to provide at least 20 cm separation from the human body at all times This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and...

Отзывы: