1. Introduction
The STG/OUT16-S2 remote modules are field mounted and connected via RS485 buses to
the control panel Mu+S2. They provide 16 Open Collector outputs (negative switch)
with programmable functions to remotely trigger Sirens, Solenoid valves, Relays, etc.
Each STG/OUT16-S module can be connected to up to 2 boards and 8 relays (optional) that
convert the Open Collector output to a powerless exchange contact.
Each module must be addressed using the rotary switches placed on the PCB. The address
must be univocal and between 1 and 255.
Please refer to the control panel manual for the appropriate module using and setting.
2. Module layout
Figure 1) Layout STG/IN8S
3. Addressing
The STG/OUT16-S2 modules are addressed using the two rotary switches in RSW 1 and 2
hexadecimals. Rotary switches permit hexadecimal settings (base 16). Each switch as 16
positions (0-F) and the pointer is positioned on the number chosen using a screwdriver to
create a decimal value between 1 and 255 (see table). For the maximum number of modules
that can be connected to the unit refer to the control panel manual.
O/C output connections
-V
+V
Outputs 9-16
Relay board connection (optional)
-V
Out 1-8
+V
++vv
CCO
OM
M
NNO
O
RRLL22
NNCC
++vv
CCO
OM
M
NNO
O
RRLL22
NNCC
+V
+V
Example of relay connection
DL1: WD Fault
DL2: TX Data
DL3: RX Data
DL4: RTS
DL5: Power ON
EOL resistor
If the module is the last of the
bus line, close JP10
Power supply (-V/+V)
RS485 serial line (B/A)
SD1-1 Communication Baud Rate setting:
ON: 115.000 bps
OFF: 9.600 bps
Rotary switches for
the module address