2.1)
STG/OUT16-S remote output module
STG/OUT16-S remote modules are field mounted and connected to the panel via RS485 buses.
They provide 16 Open Collector outputs (negative switch) with programmable functions to
remotely trigger Sirens, Solenoid valves, Relays, etc. Each STG/OUT16-S module can be
connected to up to 2 boards of 8 relays that convert the Open Collector output to a powerless
exchange contact.
Each module must be addressed using the rotary switches placed on the PCB. The address
must be univocal and between 1 and 255 (1-247 for the Modbus protocol).
For the maximum number of modules, see the table at chapter. 1- Introduction
Morsettiera alimentazione
e linea seriale
(Power supply and serial line)
Commutatori rotativi per
l’indirizzo del modulo
Jp13 Communication Baud Rate setting:
Closed 115.000 bps
(Mu+ control panel
Open 9.600 bps
(old Galileo Multiscan control panel)
Jp13 Settaggio velocità comunicazione:
Chiuso 115.000 bps
(Centrale Mul+)
Aperto 9.600 bps
(vecchia centrale Galileo Multiscan)
L
e
d
DL1: Guasto WD /WD Faul
DL2: TX Data
DL3: RX Data
DL4: RTS
Resistenza di file linea
(EOL resistor)
chiudere s
close i
è l’ultimo della linea /
f the module
is the last of the bus line
e il modulo
-V
+V -V
Morsettiera uscite O/Ci
(O/C output connections)
Outputs 9-16
Out 1-8
A
B
Rs485 serial line
Collegamento scheda relè (opzionale)
/ Relay board connection (optional)
Jumper da non manomettere
/ jumpers not to be touched
Jp5
Jp6
Jp7
Jp8
Jp9
Jp11
Jp12
Closed 1-2
Closed
Closed
Open
Open
Open
Open
Rotary switches
for the module address
+V
+V
+V
Esempio di collegamento relè
Example of relay connection
Fig. 2.4) STG/OUT16-S module