Current Source 1 Setup 

The level sensor is connected to the ORB though Current Loop 1.  For current loop setup, use the 

External

 tab on the 

ORB webpage or Senquip Portal and select the Current Loop 1 peripheral. 

1.

 

Give the current data a meaningful name; 
in this case “Water Level”. 

2.

 

Water level data is to be sent every time 
the ORB wakes up and so the Interval is 
set to 1. 

3.

 

Use the Start Time setting to apply power 
to the sensor a short time before the 
measurement is taken.  This allows the 
sensor data to stabilise before a 
measurement is taken.  Make this value 
as short as possible to save energy when 
operating off solar or AA batteries. 

4.

 

Hysteresis is applied when warnings and 
alarms are enabled.  Hysteresis prevents 
multiple alerts when the measured value 
is oscillating around an event level. 

5.

 

In this application, we have an alarm set if 
the water level goes below 1m or above 
4m.  Note that if you calibrate the sensor, 
warning and alarm settings are in the 
calibrated units. 

6.

 

Calibration in meters has been applied in 
this application.  According to the water 
level sensor, 4mA represents 1m and 
20mA represents 5m. 

7.

 

The calibrated unit in this example is 
meters (m).  Note that the ORBs 
webserver and the Senquip Portal will always report measured values in the calibrated  units; meters in this 
case.   

 

 

 

1

 

2

 

3

 

4

 

5

 

6

 

 

5

 

7

 

 

5

 

 

 

 

 

 

 

 