Senmatic InClimate Скачать руководство пользователя страница 4

Digital input

Selection guide for digital input in register 40004

Digital input, choise of below options:
1. Extended operation

(normally open or normally closed switch)

2. Pir Sensor or window relay

(normally open or normally closed switch)

InClimate selection guide in register 40003

Following set-up options are available in register 40003:
1. AC or DC (Default ”0” = AC)
2. CO2
3. RH
4. Digital input
5. Blind cover, temperature offset for blind cover to be done according to the mounting

instructions for blind cover in register 40035.

0

AC (standard)

100

DC

X

1

AC + CO2

101

DC + CO2

X

2

AC + CO2 + RH

102

DC + CO2 + RH

X

3

AC + RH

103

DC + RH

X

4

AC + Digital input

104

DC + Digital input

X

5

AC + CO2 + Digital input

105

DC + CO2 + Digital input

X

6

AC + CO2 + RH + Digital input

106

+

+

+

X

DC CO2 RH Digital input

7

AC + RH + Digital input

107

DC + RH + Digital input

X

8

AC + blind cover

108

DC + blind cover

X

9

AC + CO2 + blind cover

109

DC + CO2 + blind cover

X

10

AC + CO2 + RH + blind cover

110

DC + CO2 + RH + blind cover

X

11

AC + RH + blind cover

111

DC + RH + blind cover

X

12

AC + Digital input +

112

DC + Digital input +

blind cover

blind cover

X

13

AC + CO2 + Digital input +

113

+

DC + CO2 Digital input +

blind cover

blind cover

X

14

AC + CO2 + RH + Digital input +

114

DC + CO2 + RH +

blind cover

Digital input + blind cover

X

15

AC + RH + Digital input +

115

DC + RH +

blind cover

blind cover

X

Digital input +

Item

V

alue

307-051

T

emp-Co2-RH

Description

Description

Parameter

With digital input

Without digital input

description

with 2 x 0-10V

with 3 x 0-10V

InClimate selection guide in register 40003

307-052

T

emp-Co2

307-053

T

emp-RH

307-054

T

emp

307-001

T

emp-Co2-RH

307-002

T

emp-Co2

307-003

T

emp-RH

307-004

T

emp

103-995_V3.0

For further information:

www.senmatic.dk/sensorer/inclimate

Senmatic A/S
Industrivej 8 - DK-5471 Søndersø
Tel. 64 89 22 11 - [email protected] - www.senmatic.dk

Register 40004 - Selection guide digital input table

0

Operation switch

NO

1

Operation switch

NC

2

Pir sensor / window relay

NO

3

Pir sensor / window relay

NC

Содержание InClimate

Страница 1: ...put 307 051 Temp CO2 Digital input 307 052 Temp RH Digital input 307 053 Temp Digital input 307 054 2 x 0 10 V outputs and 1 digital input Programming tool 307 009 Description Item number Temp CO RH 307 001 2 Temp CO 307 002 2 Temp RH 307 003 Temp 307 004 3 x 0 10 V outputs Bl 307 007 ind cover Connection of cable Cables can be connected from the back or the top or the bottom via knockout blanks D...

Страница 2: ... 30 C fully scalable Accuracy 1 C of full scale Linear output 0 10 V min load 10kΩ Image no 3 CO2 measurement Measuring range 0 2000 ppm Set point function 600 1200 ppm fully scalable Accuracy 50 ppm ved 20 C ABC self calibrating Linear output 0 10 V min load 10kΩ Relative humidity measurement Measuring range 0 100 RH Accuracy 5 RH 20 95 Linear output 0 10 V min load 10kΩ Digital input Programmabl...

Страница 3: ...r Local Temperature set point and CO2 via Modbus 0 Standard local 1 via Modbus 2 Local Temperature set point and CO2 set point via Modbus c Possibility of adjustment of centre point and span on the temperature potentio meter Standard 21 C 3 C d Lokal PI regulator PI regulators control VAV1 and VAV2 There are PI parameters for CO2 and temperature for VAV1 and PI parameters for VAV2 temperature for ...

Страница 4: ...2 blind cover 109 DC CO2 blind cover X 10 AC CO2 RH blind cover 110 DC CO2 RH blind cover X 11 AC RH blind cover 111 DC RH blind cover X 12 AC Digital input 112 DC Digital input blind cover blind cover X 13 AC CO2 Digital input 113 DC CO2 Digital input blind cover blind cover X 14 AC CO2 RH Digital input 114 DC CO2 RH blind cover Digital input blind cover X 15 AC RH Digital input 115 DC RH blind c...

Отзывы: