Mode

Switch

Pos.

Mode

description

CO

2

VAV1

0-10V

Temp

VAV2

0-10V

Humi-

dity

0-10V

Transmitter-
mode

0

a. No adjustment options for temperature, CO2 and RH.

Pure transmitter-mode

.

CO2

0-2000

PPM

Temp.

0-50°C

Humidity

0-100%

Only 307-

001/003

Transmitter
mode with
setup function.

a. No adjustment options for temperature and CO2.

Pure transmitter-mode.

b. Scale button can be used for the setup function

0-10V is read off Humidity/VAV3., only applies for 307-001/003

Temp.

0-50°C

Setup

function

only 307-

001/002/

003/004

1

2

a. Fixed set point of 21 °C. The temperature can be ad/- 3 °C.
b. CO2 is adjustable from 600 to 1200 ppm on the internal potentiometer.

Standard setting 800 PPM

c. Options for VAV1 control parameter:

0=Vout1 (standard) is controlled through CO and temperature, the highest
calculated PI value is deciding.
1=Vout 1 is controlled solely through temperature. CO2 set point is ignored.
2= Vout1 is controlled solely through CO2. Temperature set point is ignored.

d. VAV1 minimum voltage 0 to 10V for ventilation damper is possible.

0=Standard 0V, 20=2V, 55=5,5V, etc.

e. Options of window functionality:

The window function works by means of the sensor constantly checking the
temperature change over a period of 5 minutes. If for example the temperature has
dropped more than five degrees during this period, the sensor will shut off the heat
(VAV2). The heat will be turned off for 20 minutes. The desired temperature change
can be set

, standard 5°C.

f. Possibility of choosing dead zone functionality:

Standard 0°C, can be activated and changed up to ±10 °C.

Standalone

Three PI
regulators
control VAV1
and VAV2.
There are PI
parameters
for CO2 and
temperature
for VAV1 and
there are PI
parameters
for VAV2
temperature
for the heat
valve
adjustment

.

3

Stand-alone
PI-adjustment

See mode 2.

a. The temperature can be adjusted between 5 °C and 30 °C.

Other setting options – see mode 2.

4

Modbus

(Also as
Stand-alone)

Data is sent
to the BMS
terminal

a. Possible to choose digital input etc. Standard setting is ”0” for register 40003 = AC.

See program guide page 4

b. Standard fixed set-point is 21°C. The temperature is adjustable ±3°C.

Set-point (temp og CO2) can be local or be changed by Modbus or Local
Temperature set-point and CO2 via Modbus. 0=Standard local, 1=via Modbus,
2 Local Temperature set-point and CO2 set-point via Modbus.

c. Possibility of adjustment of centre point and ± span on the temperature potentio-

meter. Standard 21°C, +/-3°C.

d. Lokal PI regulator.

PI regulators control VAV1 and VAV2. There are PI parameters for CO2 and
temperature for VAV1, and PI parameters for VAV2 temperature for the

heat valve

r

.

egulation

e. Options for choice of VAV1 control-parameters:

0=Vout1 (standard) is controlled through CO2 and temperature, where the highest
calculated PI-value is deciding.
1=Vout1 is controlled solely through temperature. CO2 set-point is ignored.
2=Vout 1 is controlled solely through CO2 Temperature set-point is ignored.

.

f. VAV minimum voltage 0 to 10V for ventilation damper.

0=Standard 0V, 20=2V, 55=5,5V, etc.

g. Forced opening of VAV1:

0=Standard, 1=Forced opening of VAV1 in Unoccupied mode.

h. Optional choice of window function:

The window function works through the sensor constantly checking the
temperature change over a period of 5 minutes. If for example the temperature has
dropped more than five degrees during this period, the sensor will shut off the heat.
(VAV2). The heat will be turned off for 20 minutes.
The required temperature change can be set, standard 5°C.

i. Optional choice of 3 full dead zone functionalities:

0=Occupied, standard ±1 °C.
1=Standby, standard ±3 °C.
2=Unoccupied, standard ±6°C, possibility of forced opening of VAV1 damper.

j. Possibility of choosing downdraft function:

Possibility of opening the

VAV2 heat valve percentage-wise depending on the

outdoor temperature.

5

Modbus is

controlled
from the BMS
system only.
Humidity
output only
applicable for

307-001

a. Possibility of choosing digital input etc. Standard setting is ”0” for register 40003 =

AC. See program guide page 3

b. No adjustment options for temperature, RH and CO2.

All sensor values are read via Modbus and output voltages from InClimate are

BMS

controlled from

central unit.

CO2

0-2000

PPM

VAV

control

Temp.

control

No

output

VAV

control

Temp.

control

No

control

VAV

control

Temp.

control

No

control

Controlled

from
CTS

O
N

1 2 3

7

Forced
control

a. Forced opening (VAV1, VAV2, VAV3) 10V

cannot be used for

with

VAV3,

InClimate

digital input.

VAV1

VAV2

VAV3

InClimate functions and various functions are changed via Modbus
or InClimate programming tool (ordering number 307-009)

Humidity
output
Only 307-
01/002/
003/004

Controlled

from
CTS

Содержание InClimate

Страница 1: ...put 307 051 Temp CO2 Digital input 307 052 Temp RH Digital input 307 053 Temp Digital input 307 054 2 x 0 10 V outputs and 1 digital input Programming tool 307 009 Description Item number Temp CO RH 307 001 2 Temp CO 307 002 2 Temp RH 307 003 Temp 307 004 3 x 0 10 V outputs Bl 307 007 ind cover Connection of cable Cables can be connected from the back or the top or the bottom via knockout blanks D...

Страница 2: ... 30 C fully scalable Accuracy 1 C of full scale Linear output 0 10 V min load 10kΩ Image no 3 CO2 measurement Measuring range 0 2000 ppm Set point function 600 1200 ppm fully scalable Accuracy 50 ppm ved 20 C ABC self calibrating Linear output 0 10 V min load 10kΩ Relative humidity measurement Measuring range 0 100 RH Accuracy 5 RH 20 95 Linear output 0 10 V min load 10kΩ Digital input Programmabl...

Страница 3: ...r Local Temperature set point and CO2 via Modbus 0 Standard local 1 via Modbus 2 Local Temperature set point and CO2 set point via Modbus c Possibility of adjustment of centre point and span on the temperature potentio meter Standard 21 C 3 C d Lokal PI regulator PI regulators control VAV1 and VAV2 There are PI parameters for CO2 and temperature for VAV1 and PI parameters for VAV2 temperature for ...

Страница 4: ...2 blind cover 109 DC CO2 blind cover X 10 AC CO2 RH blind cover 110 DC CO2 RH blind cover X 11 AC RH blind cover 111 DC RH blind cover X 12 AC Digital input 112 DC Digital input blind cover blind cover X 13 AC CO2 Digital input 113 DC CO2 Digital input blind cover blind cover X 14 AC CO2 RH Digital input 114 DC CO2 RH blind cover Digital input blind cover X 15 AC RH Digital input 115 DC RH blind c...

Отзывы: