I N S TA L L AT I O N

The Model HF-RES must be installed in accordance with the following instructions:

NOTES

Do not use sprinklers which have been subjected to potential mechanical damage. Do not use sprinklers which show deformation 
or cracking in either the sprinkler or protection cap.

The Protective Cap must remain on the sprinkler during installation and until the ceiling installation is completed. The Protective 
Cap must be removed to place the sprinkler in service.

Use a torque of 7 to 14 ft·lbs (9.5 to 19.0 N·m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended maximum 
torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler.

Use only HF-H model wrench socket for installation of HF-RES sprinklers. Use of any other wrench or socket is prohibited and 
may cause damage to the sprinkler.

Do not attempt to compensate for insufficient adjustment in an Escutcheon Plate by under- or over-tightening the sprinkler. 
Readjust the position of the sprinkler fitting to suit.

Installation Steps

Step 1: 

The sprinkler must be installed only in the sidewall position 

with their centerline of waterway perpendicular to the back wall 
and parallel to the ceiling. The word “TOP” on the sub-deflector 
has to face towards the ceiling with the front edge of the sub-
deflector parallel to the ceiling.

Step 2: 

Install the sprinkler fitting so that the distance from the 

face of the fitting to the mounting surface will be nominally 53/64 
inch (21.0mm) as shown in Figure 3.

Step 3: 

With pipe thread sealant applied to the pipe threads, hand 

tightens the Sprinkler into the sprinkler fitting. 

 

  FIGURE 1 

MODEL 

  K=4.2  RESIDENTIAL  FLUSH  HORIZONTAL 

SIDE-WALL SPRINKLER

 

Year of Manufacture

Temperature Rating (162 F)

Listing Mark

Country Origin

I.D Number (SIN)

Marking

Four Wrench Slots

5-Cover (Copper)

7-Fusible Metal

2-Frame (Bronze)

1-Body (Copper Alloy)

6

6-Heat Collector (Copper)

8-Sub Deflector (Copper Alloy)

4-Gasket (PTFE)

3-Deflector (Copper Alloy)

COMPONENTS (MATERIALS) :

7

4

1/2" NPT

2- 7/16"

2

1 3

8 5

9-Valve Cap (Copper Alloy)

9

  FIGURE 2 

Normal Condition

Operation

Water Discharge

 

  FIGURE 4 

Ratchet

Socket HF-H

Protective Cap

 

  FIGURE 3 

53/64"

MOUNTING SURFACE

CENTER MARK

Min. 1/8" (3mm)

MAKE A SPACE HERE

2-

 3

/8

" (

60

m

m

)

W

ALL

 H

OL

E

D

IA

M

ET

ER

DO NOT

OVER-TIGHTEN

BODY

REDUCER

REDUCER

CORRECT

INCORRECT

TOLERANCE LIMIT OF

BACK-WALL LEVEL

WALL

WALL SURFACE

WALL

 

  FIGURE 5 

Cap Removal Tool

Groove of cap

Step

2

Pull out

Ste

p 1

HF-RES Sprinkler

Protective Cap

 

  FIGURE 6 

ESCUTCHEON

MOUNTING

SURFACE

WALL

TOP OF

DEFLECTOR

 

  FIGURE 7 

ESCUTCHEON

ESCUTCHEON

THERE MUST

NOT BE SPACE

MOUNTING SURFACE

CORRECT

ESCUTCHEON

INCORRECT

INCORRECT

WALL

Figure 3:

 Installation

Figure 4:

 Ratchet & Socket

Step 4: 

Wrench tighten the Sprinkler using only the Socket 

HF-H or Ratchet (3/8

 drive) & Socket HF-H Combination (Ref. 

Figure 4). Put the Sprinkler Socket over the sprinkler without 
the sub-deflector hit till the socket touches the body of the 
sprinkler. Turn the socket till the wrench recess of the Socket 
can be applied to the sprinkler wrenching area (Ref. Figure 4).

Special care must be exercised to avoid damage to the sprinkler 
while you remove the socket wrench from the sprinkler as well.

 

  FIGURE 1 

MODEL 

  K=4.2  RESIDENTIAL  FLUSH  HORIZONTAL 

SIDE-WALL SPRINKLER

 

Year of Manufacture

Temperature Rating (162 F)

Listing Mark

Country Origin

I.D Number (SIN)

Marking

Four Wrench Slots

5-Cover (Copper)

7-Fusible Metal

2-Frame (Bronze)

1-Body (Copper Alloy)

6

6-Heat Collector (Copper)

8-Sub Deflector (Copper Alloy)

4-Gasket (PTFE)

3-Deflector (Copper Alloy)

COMPONENTS (MATERIALS) :

7

4

1/2" NPT

2- 7/16"

2

1 3

8 5

9-Valve Cap (Copper Alloy)

9

  FIGURE 2 

Normal Condition

Operation

Water Discharge

 

  FIGURE 4 

Ratchet

Socket HF-H

Protective Cap

 

  FIGURE 3 

53/64"

MOUNTING SURFACE

CENTER MARK

Min. 1/8" (3mm)

MAKE A SPACE HERE

2-

 3

/8

" (

60

m

m

)

W

ALL

 H

OL

E

D

IA

M

ET

ER

DO NOT

OVER-TIGHTEN

BODY

REDUCER

REDUCER

CORRECT

INCORRECT

TOLERANCE LIMIT OF

BACK-WALL LEVEL

WALL

WALL SURFACE

WALL

 

  FIGURE 5 

Cap Removal Tool

Groove of cap

Step

2

Pull out

Ste

p 1

HF-RES Sprinkler

Protective Cap

 

  FIGURE 6 

ESCUTCHEON

MOUNTING

SURFACE

WALL

TOP OF

DEFLECTOR

 

  FIGURE 7 

ESCUTCHEON

ESCUTCHEON

THERE MUST

NOT BE SPACE

MOUNTING SURFACE

CORRECT

ESCUTCHEON

INCORRECT

INCORRECT

WALL

Step 5: 

Use the “tolerance limit of back-wall level” indicator on the Protective Cap to check for proper installation depth 

(Ref. Figure 3) Relocate the sprinkler fitting as necessary. If desired the Protective Cap may also be used to locate the 
center of the clearance hole by gently pushing the back wall material against the center point of the Cap.

Step 6: 

After the back wall has been completed with the 2-3/8inch (60mm) diameter clearance hole, use the Protective 

Cap Removal Tool (Ref. Figure 5) to remove the Protective Cap and then push on the Escutcheon until its flange just 
comes in contact with the back wall (Ref. Figures 6 & Figure 7). 

Содержание HF-RES

Страница 1: ...pressures enabling smaller pipe sizes and water supply requirements The flush design of the Model HF RES features a separable escutcheon providing 3 16 inch 4 7 mm of total adjustment This adjustment...

Страница 2: ...nklered in accordance with the recommendations of NFPA 13 13D or 13R In the event of this condition consult the authorities having jurisdiction for guidance and approval It is the responsibility of th...

Страница 3: ...ly the escutcheon provided with the Model HF RES The sprinkler must be secured in position by firmly fastening the sprinkler system piping to the structure If the sprinkler is not properly secured in...

Страница 4: ...er smooth flat horizontal ceilings as outlined in the applicable installation standard recognized by the approval agency e g UL recognizes NFPA 13 13D and 13R The distance from the Top of the sub defl...

Страница 5: ...9 FIGURE 3 53 64 MOUNTING SURFACE CENTER MARK Min 1 8 3mm MAKE A SPACE HERE 2 3 8 60mm WALL HOLE DIAMETER DO NOT OVER TIGHTEN BODY REDUCER REDUCER CORRECT INCORRECT TOLERANCE LIMIT OF BACK WALL LEVEL...

Страница 6: ...ve Cap MOUNTING SURFACE WALL TOP OF DEFLECTOR FIGURE 7 ESCUTCHEON ESCUTCHEON THERE MUST NOT BE SPACE MOUNTING SURFACE CORRECT ESCUTCHEON INCORRECT INCORRECT WALL C A RE M A INTE N A NCE The following...

Страница 7: ...under Hydraulic Design Criteria When remodeling such as by adding false beams or light fixtures or changing the location of compartment walls first verity that the new construction will not violate t...

Отзывы: