Page
:
6 of 6
Document No.U029323
Date
:
Jun/17/2014
Do NOT clean the sprinklers with soap and water, detergents, ammonia, cleaning fluids, or other chemicals. Remove
dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a
soft bristle (i.e., dusting) brush attachment.
Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire
development and spread of these materials can reduce the ability of the sprinkler systems to aid in the control of a fire
involving such hazards.
Leaking or corroded sprinklers must be replaced.
Automatic Sprinklers must never be shipped or stored where the temperature exceeds 100°F / 38°C.
Automatic sprinkler must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the
sprinklers have been in any way modified, they must be replaced.
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation. Damaged
units, as a result of dropping, hitting, over-tightening, or wrench slippage, must be replaced.
When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first verity that
the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter the new construction
and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations.
The owner is responsible for the maintenance of the sprinkler system, including inspection and testing, its compliance with this
documents, as well as the standards of the National Fire Protection Association (e.g., NFPA 25), and the regulations of any other
authorities having jurisdiction. The owner should direct any questions regarding the above rules and regulations to the installing
contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested, and
maintained by a qualified Inspection Service in accordance with NFPA 25.
ORDER PROCEDURE
When placing an order, please contact a local distributor with the following information (Model Name, Specify, Temp. and Finish).
Sprinkler:
Model: CN-QR (SS9521, Quick & Standard Response, Standard Coverage, Flat Concealed Sprinkler, Pendent, K5.6)
Temp.
Model
162°F / 72°C
205°F / 96°C
CN-QR K5.6
○
○
※
1
※
1:
c
UL
us
listed only
Cover Plate Assembly:
2-3/8inch (60mm), Order Separately from Sprinkler
Please refer to the chart below for available temperature and finishes.
Standard Finishes
Custom Finishes
White Ivory Beige Brown
Black Nickel
Wood
Grain
Custom
Color Custom
Pattern
2-3/8" Round, 140ºF
○
○
○
○
○
○
○
○
○
2-3/8" Round, 162ºF
※1
○
-
-
-
-
-
-
○
○
※
1:
c
UL
us
listed only
Tools for Installation of Model: CN-QR
Socket for Model CN-QR
Wrench & Socket for Model CN-QR
Protective Cap Removal Tool for Model CN-QR