MI00065-3-EN
INSTALLATION MANUAL
3/4
ERRORS REGARD FIELD OF INPUT MEASUREMENT AND WITH INPUT > 10% OF THE SCALE.
Frequency band
Calibration error
Thermal coefficient
Linearity error
Other
20 ÷ 400Hz sinus.
0.3%
0.02%/°C
0.1%
1% max for EMC
400 ÷ 1000Hz sinus.
0.5%
0.02%/°C
0.2%
1% max for EMC
SETTING THE DIP-SWITCHES
On the side of the module there are dip switches that can be used to select the desired functions. To select these
functions, set the DIP switches as shown in the tables:
SW1 DIP-SWITCH SETTINGS
DIP 1
DI2
ON
4..20mA / 1..5V / 2..10V
ON
0..10V / 2..20V
OFF
0..20mA / 0..5V / 0..10V
OFF
0..5V / 1..5V
INSTALLATION REGULATIONS
The module has been designed for vertical installation on a DIN 46277 rail. For optimal operation and long life,
adequate ventilation must be provided. Avoid positioning ducting or other objects that obstruct the ventilation slots.
Avoid mounting modules over heat-generating equipment. Installation in the bottom part of the electrical panel is
recommended.