MI00065-3-EN
INSTALLATION MANUAL
2/4
MODULE LAYOUT
SIGNALS VIA LED ON FRONT PANEL
LED
STATUS
LED meaning
PWR
On
Device powered
Off
Device not powered
Dimensions LxHxD:
17.5 x 102.5 x 111 mm;
Weight:
110 g;
Enclosure:
PA6, black
SW1
111
m
m
17.5 mm
102.5 mm
TECHNICAL SPECIFICATIONS
CERTIFICATIONS
https://www.seneca.it/products/z201/doc/CE_declaration
POWER SUPPLY
Voltage: 19
÷
40 Vdc; 19
÷
28 Vac 50
÷
60 Hz, max.: 2.5W
INPUT
Current: 0
÷
5 AaC or 0
÷
10 AaC settable by terminal panel.
Insulation 3700 Vac.
OUTPUT
Current 0
÷ 20 or 4 ÷
20 mA, maximum load 600 Ohm;
Voltage 0
÷
10 or 0
÷
5 Vdc, 2
÷
10 or 1
÷
5 Vdc.
Minimum load 2500 Ohm.
ENVIRONMENTAL
CONDITIONS
Operating temperature: from -20°C to +55°C
Humidity: 10% ÷ 90% non condensing.
Storage temperature: from -30°C to +85°C
Protection rating: IP20
RESPONSE TIME
< 200 ms
PERMISSIBLE
OVERLOAD
12A continuative, 30A for 1 s.
POWER
SUPPLY/OUTPUT
PROTECTION
against impulse voltage overload 400W/ms.
INSTALLATION
CLASS
III, it can be applied on a three-phase network of up to 500 Vac phase-phase,
300Vac phase-ground.
1 2 3
4 5 6
7 8 9
10 11 12