background image

ENGLISH 3/8

MI004301-E

3.3 CONNECTIONS

USB Interface

Micro USB connector (frontal panel)

3.4 POWER SUPPLY

Supply Voltage

10-40 V

, 19-28 V

 50-60 Hz, 

through screw terminals: 2 – 3

Power supply unit

Classe 2

Power consumption

1.6 W @ 24 V

 with output 20 mA;

 Max: 2.5 W

3.5 MODULE CASE

Case

PA6, black color

Dimensions

Width L=100mm; Height H=112mm; Depth W=17,5mm

Board terminals

2

Removable 3 way screw terminals: pitch 5.08mm, section 2.5mm

Protection class

IP20

3.6 ENVIRONMENTAL CONDITIONS

Operating
Temperature

-10°C – +60°C (UL: -10°C – +60°C)

INSULATIONS 1500V

STANDARDS

The module complies with the following standards:

EN61000-6-4 (

electromagnetic emission,

in industrial environment

)

EN61000-6-2 (

electromagnetic immunity,

in industrial environment)

EN61010-1 (safety)
Notes:
- Use with copper conductor.
- Use in Pollution Degree 2 Environment
- Power Supply must be Class 2
- When supplied by an Isolated Limited Voltage and/or
  Limited Current power supply, a fuse rated max 2.5 A
  shall be installed in the field.

1500 V

 insulating voltage is among: 

- power supply 
- analog input
- analog output

2

3

6

USB

POWERSUPPLY

1

ANALOG

OUT

10

11

12

9
8
7

1500 V

V - mA

INPUT

Errors referred to maximum
measuring range:

Calibration

Error

Thermal

Coefficient

Linearity

Error

EMI (1)

Voltage / Current input

0.1%

0.01%/°K

0.05 %

<1%

Voltage output (2)

0.3%

0.01%/°K

0.01%

(1) EMI: electromagnetic interference.
(2) Values to be added to the errors of the selected input.

Содержание Z109UI2

Страница 1: ...9 8706287 Internet site Technical assistance www seneca it support seneca it Commercial reference sales seneca it Chapter index Page 1 Preliminary warnings 2 2 Description and characteristics 2 1 Modu...

Страница 2: ...d Measurement and re transmission on isolated analog output with voltage and current output DIP switch for selecting type of input START END output mode zero elevation scale inversion output type mA o...

Страница 3: ...ards EN61000 6 4 electromagnetic emission in industrial environment EN61000 6 2 electromagnetic immunity in industrial environment EN61010 1 safety Notes Use with copper conductor Use in Pollution Deg...

Страница 4: ...y at least 5 mm in the following cases If the panel operating temperature exceeds 45 C and at least one of the severe operating conditions exists If the panel operating temperature exceeds 35 C and at...

Страница 5: ...tput 1 6 V Voltage mA output 1 6 A Generated current 3 mA output External power Supply current 4 1 6 A 5 6 ANALOG OUTPUT Electrical ratings for UL Output 10 V 20 mA Input 20 V 20 mA Operating Temp 20...

Страница 6: ...e START and END scale desired SW1 INPUT SELECTION POSITIO N INPUT POSITION INPUT 1 2 3 4 TYPE 1 2 3 4 TYPE V mA SW2 START and END POSITIO N START POSITIO N END 1 2 3 SCALE n 4 5 6 SCALE n 1 1 2 2 3 3...

Страница 7: ...the type of input START and END measurement which include the required beginning and end values 2 Power up the module 3 Supply a calibrator or simulator of the signal you wish to measure and re transm...

Страница 8: ...d information about the recycling of the product please contact your local city office waste disposal service of the retail store where you purchased this product 9 DECOMMISSIONING AND DISPOSAL 8 MODU...

Отзывы: