ENGLISH 3/8
MI004301-E
3.3 CONNECTIONS
USB Interface
Micro USB connector (frontal panel)
3.4 POWER SUPPLY
Supply Voltage
10-40 V
, 19-28 V
50-60 Hz,
through screw terminals: 2 – 3
Power supply unit
Classe 2
Power consumption
1.6 W @ 24 V
with output 20 mA;
Max: 2.5 W
3.5 MODULE CASE
Case
PA6, black color
Dimensions
Width L=100mm; Height H=112mm; Depth W=17,5mm
Board terminals
2
Removable 3 way screw terminals: pitch 5.08mm, section 2.5mm
Protection class
IP20
3.6 ENVIRONMENTAL CONDITIONS
Operating
Temperature
-10°C – +60°C (UL: -10°C – +60°C)
INSULATIONS 1500V
STANDARDS
The module complies with the following standards:
EN61000-6-4 (
electromagnetic emission,
in industrial environment
)
EN61000-6-2 (
electromagnetic immunity,
in industrial environment)
EN61010-1 (safety)
Notes:
- Use with copper conductor.
- Use in Pollution Degree 2 Environment
- Power Supply must be Class 2
- When supplied by an Isolated Limited Voltage and/or
Limited Current power supply, a fuse rated max 2.5 A
shall be installed in the field.
1500 V
insulating voltage is among:
- power supply
- analog input
- analog output
2
3
6
USB
POWERSUPPLY
1
ANALOG
OUT
10
11
12
9
8
7
1500 V
V - mA
INPUT
Errors referred to maximum
measuring range:
Calibration
Error
Thermal
Coefficient
Linearity
Error
EMI (1)
Voltage / Current input
0.1%
0.01%/°K
0.05 %
<1%
Voltage output (2)
0.3%
0.01%/°K
0.01%
(1) EMI: electromagnetic interference.