background image

ENGLISH 2/8

MI004301-E

Voltage input:

Bipolar    from  100  mV  up  to  20  V  in  9  scales,  input  impedance  1  M

,

resolution max 15 bit + sign.

Current input:

Bipolar up to 20 mA, input impedance ~ 50 

, resolution: 1

A.

Sampling frequency:

240 sps with 11 bits resolution.

Response time:

35 ms with 11 bits resolution.

3. TECHNICAL SPECIFICATIONS

3.1 INPUT

2.2 GENERAL CHARACTERISTICS AND FEATURES

 input type: 

V  or  mA.

Voltage or current

Sensor powered by 2-wire technique: 20 V

 stabilised, 20mA max

,

 short-circuit

 

protected

.

Measurement and re-transmission on isolated analog output, with voltage and current output.

DIP-switch for selecting: type of input, START-END, output mode 

 

(zero elevation, scale inversion), output type (mA or V ).

Front panel indicating: power on, off scale or setting error.

3-points insulation: 1500 V

.

Output:

I: 0-20 / 4-20 mA, max load resistance 600 

V: 0-5 V / 0-10 V / 1-5 V / 2-10 V, min load resistance 2 k

Resolution: 2.5 

A / 1.25 mV.

Data memory:

EEPROM for all configuration data; storage time: 40 years.

3.2 OUTPUTS

The Z109UI2 module acquires an voltage or current input signal, converts it to an analog format and send it to 
an universal isolated output.

2. DESCRIPTION AND CHARACTERISTICS

2.1 MODULE DESCRIPTION

Содержание Z109UI2

Страница 1: ...9 8706287 Internet site Technical assistance www seneca it support seneca it Commercial reference sales seneca it Chapter index Page 1 Preliminary warnings 2 2 Description and characteristics 2 1 Modu...

Страница 2: ...d Measurement and re transmission on isolated analog output with voltage and current output DIP switch for selecting type of input START END output mode zero elevation scale inversion output type mA o...

Страница 3: ...ards EN61000 6 4 electromagnetic emission in industrial environment EN61000 6 2 electromagnetic immunity in industrial environment EN61010 1 safety Notes Use with copper conductor Use in Pollution Deg...

Страница 4: ...y at least 5 mm in the following cases If the panel operating temperature exceeds 45 C and at least one of the severe operating conditions exists If the panel operating temperature exceeds 35 C and at...

Страница 5: ...tput 1 6 V Voltage mA output 1 6 A Generated current 3 mA output External power Supply current 4 1 6 A 5 6 ANALOG OUTPUT Electrical ratings for UL Output 10 V 20 mA Input 20 V 20 mA Operating Temp 20...

Страница 6: ...e START and END scale desired SW1 INPUT SELECTION POSITIO N INPUT POSITION INPUT 1 2 3 4 TYPE 1 2 3 4 TYPE V mA SW2 START and END POSITIO N START POSITIO N END 1 2 3 SCALE n 4 5 6 SCALE n 1 1 2 2 3 3...

Страница 7: ...the type of input START and END measurement which include the required beginning and end values 2 Power up the module 3 Supply a calibrator or simulator of the signal you wish to measure and re transm...

Страница 8: ...d information about the recycling of the product please contact your local city office waste disposal service of the retail store where you purchased this product 9 DECOMMISSIONING AND DISPOSAL 8 MODU...

Отзывы: