ENGLISH 7/16
MI004202-E
The START and END push-buttons under the SW2 DIP-switch group allow to set the beginning and end
scale at will, within the scale pre-set through the dip-switches. To obtain this facility it is necessary to use
a suitable signal generator, able to furnish the desidered values of beginning and end scale.
The procedure is following:
1. Set through dip-switches the type of input, START and END measurement which include the required
beginning and end values.
2. Power up the module.
3. Supply a calibrator or simulator of the signal you wish to measure and re-transmit.
4. Set the required START value on the calibrator (or other instrument).
5. Press the START push-button for at least 3 sec. The green LED on the front panel flashes to indicate
the value has been stored.
6. Repeat points 4 and 5 for the required END value.
7. Power off the module and set to OFF position the dip-switches of group SW2, correspondent to the
settings of START and END values.
The module is now configured for the required start and end scale.
In order to re-program it (e.g. for a different type of input) repeat the whole procedure.
SW2: SCALE AND MODE OUTPUT
POSITION
OUTPUT
POSITION OUTPUT
7 8
RANGE
7 8
MODE
z
X
0..20mA / 0..10V
X
z
NORMAL
y
X
4..20mA / 2..10V
X
y
REVERSE
SW3: OUTPUT TYPE
POSITION
OUTPUT
POSITION
OUTPUT
1 2
TYPE
1 2
TYPE
y
z
VOLTAGE
y
z
CURRENT
LEGENDA
y
ON
z
OFF
6.4 CONFIGURATION THROUGH A PC
By using a PC and EASY SETUP software, it is possible to set other normally fixed parameters in addition
to start and end scale:
Additional input types: digital filter (normally disabled), square root extraction (normally disabled), negative
burn-out (normally positive), alarm(normally set as error signalling, start and end scale of the analog output,
value of the analog output in case of error, rejection programmable for 50 or 60 Hz mains frequency (normally
set to 50 Hz), sampling frequency/resolution (normally set to 15 sps/16 bit), 3 or 4 wires measure for thermal
resistance (normally set to 3 wires) and action of the digital output alarm in case of fault.
Instructions for setting and the connection cable are supplied with the software (this must be requested
as an accessory item).
6.2 START
END
AND
SETTING AT WILL
SW2 group DIP-switches 7 and 8 enable you to set the output with or without zero elevation and/or
as a normal or reversed output. The SW3 DIP-switch group enables you to select the output type.
Note:The DIP-switches must be set while the module is powered down, avoiding electrostatic
discharge, otherwise the module may be damaged.
6.3
E
OUTPUT SEL CTION
SW1: INPUT SELECTION
POSITION
INPUT
POSITION
INPUT
1 2 3 4
TYPE
1 2 3 4
TYPE
z z z z
V
y
z z z
Tc K
y
z z z
W
/ Rheostat
y
y
z z
Tc R
y
z
z z
mA
y
y
z
z
Tc S
y
y
z z
NI100
y
y
y
z
Tc T
y
z z
z
PT100
y
y
z z
Tc B
y
y
z
z
PT500
y
y
y
z
Tc E
y
y
z
z
PT1000
y
y
y
z
Tc N
y
y
y
z
Tc J
y
y
y
y
Potentiometer
SW2: START e END
POSITION
START
POSITION
END
1 2 3
SCALE n°
4 5 6
SCALE n°
z z z
1
z z z
1
y
z z
2
y
z z
2
y
z
z
3
y
z
z
3
y
y
z
4
y
y
z
4
y
z z
5
y
z z
5
y
y
z
6
y
y
z
6
y
y
z
7
y
y
z
7
y
y
y
8
y
y
y
8