MI002273-E
ENGLISH 3/8
Output ripple
< 40 mV
Output regulation
< 1%
Dynamic regulation
< 1%
Turn-off time
15 ms @ 120 Vac, 60 ms @ 230 Vac
Max resistive load
15 Ω
Max capacitive load
3000 µF
3.2 Power supply/ input
Rated voltage
110- 240 V @ 50..60 Hz
Input range for AC power supply
100- 265 V @ 47-63 Hz; 110-315 Vdc
Current consumption
Max 0.7A @ 100V; 0.27 A @ 265 V
External input fuse
(recommended)
2 A, type T
Internal input fuse
1.25 A, type T (delayed), it can not be replaced
Inrush current limitation (plug in)
<25 A
Power factor
>0.60
Start-up voltage with full load
~100 Vac (with load: 15 Ω)
Shut-down voltage
~90Vac
Derating curve for output, the derate
starts at 55 °C for 0.02 A/K
Temperature (°C)
-20 0
55
70
1.5 A
1.2 A
Current (A)
3.4 Output relay, «power-good»
Relay type
N.O. with 1 A / 30 Vdc (resistive)
Relay activation
Output voltage > 23.5 Vdc
3.3 Output voltage
Max output current
1.5 A
Over-load limit current
1.7 A
Load regulation
< 1%
Rated ripple
< 50 mVpp
Protection against the short-circuit
and over-load
Yes, hiccup @ over-load limit with auto reset
3.5 Enclosure
Dimension
100 x 35 x 111 mm
Box; protection class
Black plastic, IP20 (International protection)
Weight
215 g
Temperature (°C)
Output voltage
24 Vdc ± 2 %
Output redundancy (more Z-SUPPLY
modules)
The output of a Z-SUPPLY can be parallel-connected with
the output of another Z-SUPPLY(
only
by IDC10);see fig.6