background image

General Specifications

?

6 opto-insulated digital inputs with a common contact. Internal or external power

supply of inputs selectable with a jumper.

?

Protection of inputs by TVS 600 W/ms transient suppressors.

?

Insulation of the 1500 Vac inputs  with respect to the remaining low voltage circuits.

?

2 SPST relay outputs with common contact, capacity of 2 AAC1 250 Vac. Selection of 
N.O. or N.C. contact for each relay with a jumper.

?

3750 Vac insulation between the outputs and the remaining low voltage circuits.

?

Internal logic for commanding motors, pneumatic valves and motorised valves, with 

management of thermal protection, feedback, travel limit and alarm.

?

RS485 serial communication with Modbus-Rtu protocol, 64 nodes maximum 

(without repeater). Configurable via dip-switch also.

?

Communication times shorter than 10 ms (@ 38400 Baud).

?

Connection distance up to 1200 m.

2

?

Pull-out terminals, with 2.5 mm  cross-section 

?

Facilitated wiring of power supply and serial connection by means of a bus which can 

be housed in the DIN guide.    

?

Module can be fitted on and removed from bus without interrupting communication or

power supply to the system.

MI000944-I-E

MI000944-I-E

MI000944-I-E

ENGLISH 6/13

Z-PC Line

Z-PC Line

Z-D-IO

Z-D-IO

SENECA s.r.l.

 Via Germania, 34 - 35127  -  Z.I. CAMIN - PADOVA - ITALY
 Tel.  +39.049.8705355 - 8705359  -  Fax +39.049.8706287
 For a manual and configuration software, see www.seneca.it

MI000944-I-E

EN

EN

This document is property   of SENECA srl. Duplication and reprodution are forbidden, if not     authorized. 
Contents of the present documentation refers to products and technologies described in it. All technical data 
contained in the document may be modified without prior notice Content of this documentation is subject to 
periodical revision.

ENVIRONMENTAL CONDITION

CONNECTIONS

DIMENSIONS / BOX

Voltage

Consumption

10 ..40 V

DC

 

 

19 ..28 V

AC 

a 50 ..60 Hz

Typical: 1.5 W, Max: 2.5 W

Temperature

Humidity

Altitude

Storage 
Temperature

Protection

-10 ..+65°C

30 ..90% a 40°C non condening

Up to 2000 m a.s.l.

-20 ..+85°C

IP20

Connections

Removable 3-way crew terminals, 3,5 pitch

Rear IDC10 connector for DIN 46277 rail

Dimensioni

L: 100 mm; H: 112 mm; W: 17,5 mm

PBT, colore nero

ISOLAMENTI

STANDARDS

1500 V

AC

 a tre punti:

The module complies with the following standards:

EN61000-6-4/2002-10 

emission, industrial environment).

(electromagnetic 

EN61000-6-2/2006-10

 

immunity,  industrial environment)

(electromagnetic 

EN61010-1/2001

 (safety). 

isolated  from  the  other  circuits  under 
dangerous voltage with double isolation. The 
power   supply transformer must comply with 
En60742:  “Isolated  transformers  and  safety 
transformers”.

All circuits must be 

Contenitore

ADDITIONAL NOTES 

.

Use in Pollution Degree 2 Environment 
Power Supply must be Class 2.
When supplied by an Isolated Limited Voltage/Limited Current power supply a fuse rated max 
2.5 A shall be  installed in the field.

ISOLATIONS

POWER SUPPLY

Installation Rules

Electrical Connections

The module is designed to be installed in vertical position on a DIN 46277 rail. In order to 
ensure optimum performance and the longest working life, the  module(s) must be supplied 
adequate  ventilation  and  no  raceways  or  other  objects  that  obstruct  the  ventilation  slots. 
Never install modules above sources of heat; we recommend    installation in the lower part of 
the control panel.

As it is illustrated in the next figure:

1)  Insert  the  rear  IDC10  connector  on  a  DIN  rail 
free  slot  (the  inserting  is  univocal  since  the   
connectors are polarized).

2) Tighten  the two locks placed at the sides of the 
rear IDC10 connector to fix the module.

POWER SUPPLY AND MODBUS INTERFACE

Power Supply and CAN/MODBUS interface are available by using the bus for the Seneca 
DIN rail, by the rear IDC10 connector or by Z-PC-DINAL2-17,5 accessory.

Rear Connector (IDC10)

Z-PC-DINAL2-17,5 Accessory Use

In the figure the meaning of the IDC10 
connector pins is showed, in the case 
the user decides to provide the signals 
directly through it.

In  case  of  Z-PC-DINAL-2-17,5 
accessory    use,  the  signals  may  be 
provided  by  terminal  blocks.  The 
figure  shows  the  meaning  of  the 
terminals and the position of the DIP-
switch  (present  on  each  DIN  rail 
supports listed on Accessories) for 
 network termination (not used in case 
of Modbus network). 
GNDSHLD:  Shield  to  protect  the 
connection cables ( recommended). 

Inserting on the DIN rail

ENGLISH 1/13

ENGLISH 3/13

ENGLISH 5/13

ENGLISH 7/13

1) Install the modules on the DIN rail (max 120).
2) Connect the remote modules using cables of proper length. On the table the following data 
about the cables length are provided:
-Bus Length: Modbus network maximum length as a function of the Baud rate. It is the lenght 
of the cables which connect the two bus terminators modules (see Scheme 1).
-Drop Length: maximum length of a drop line 2 m (see Scheme 1).

Scheme 1

For the best performances, the use of special shielded cables is recommended (BELDEN 
9841 cable for example).

Modbus connection rules

MI000944-I-E

DIP-switch settings

The DIP-switches position defines the module Modbus communication parameters: Address 
and Baud Rate. In the following figure the Baud Rate and Address values are listed as a 
function of the DIP-switches position:

Note

: when switches from 3 to 8 are in OFF, comunication settings are retrieved from 

EEprom

Digital Inputs

MI000944-I-E

MI000944-I-E

MI000944-I-E

ENGLISH 2/13

ENGLISH 4/13

MODULE:  6 DIGITAL INPUTS, 2 RELAY
OUTPUTS, MODBUS COMMUNICATION
ON RS485

MODULE:  6 DIGITAL INPUTS, 2 RELAY
OUTPUTS, MODBUS COMMUNICATION
ON RS485

Contents:

- General characteristics
- Technical specifications
- Installation rules
- Electrical connections
- Digital inputs
- Digital outputs
- DIP-switch settings
- Modbus connections rules
- Module configuration
- Alarm delay DIP-Switch (SW2-3 e         
SW2-4)
- Logical schemes
- LEDs Signallings
- Factory settings

Installation

Manual

Installation

Manual

Technical specifications

INPUTS

Reed, Contact, Proximity PNP, 
NPN (with external resistoor) etc...

Type input

Number of Channels

Transition level

U

H

 (stato ON)

Outputs

6

10 V

DC 

, 3 mA ± 10%

12 ..30 V

DC

, I > 3 mA

 

2 SPST relay outputs with common contact, 
capacity 5A

 250Vac. Internal jumpers for 

AC1

selecting an NO or NC contact for each relay.
     

Discrimination limits

according to IEC1131.2 tipo 1

OUTPUTS

Minimum pulse lenght

20 ms

Number of Channels

2

Operate / release time delay 

5/2 ms

Sensors  REED,  PROXIMITY  PNP,  NPN, 
contact,  can  be  connected  to  the  input 
terminals.  The  power  supply  to  these 
sensors can be obtained directly from the Z-
D-IO Module (factory configuration),or it can 
be externally supplied.
Procedure for modifying the configuration of 
the  inputs:  open  the  side  lid  and  shift  the 
configuration  jumper  J1  to  position  Int  for 
internal power supply, or in position Ext for 
external power supply (see fig. 2).

fig.2

CONTACT
10 - 12

CONTACT
11 - 12

NA
NC

J2

J3

J1

Ext

Int

SW1

SW2

Enable

NA
NC

Disable

Input power
supply

Terminat.   J4

  Internal Power supply                                Exsternal Power supply

For the meanings of the inputs, see section "Module Configuration".

The relay outputs can be configured to use the NO contact (factory configuration), or the 
NC contact. To change the output configuration, open the side lid and shift the 
configuration jumpers J2 and J3 (see fig.2).

1

7

4

10

2

8

5

11

3

9

6

12

+VI

IN1

IN2

IN3

IN4

IN5

IN6

1

7

4

10

2

8

5

11

3

9

6

12

+VE

IN1

IN2

IN3

IN4

IN5

IN6

fig.3

fig.4

Digital outputs

The module can be configured by the SW2 Dip-switch in order to function in four different 
operating  modes:

Terminal

Terminal

Terminal

Teminal

INPUTS

INPUTS

I/O MODALITY

MOTOR COMMAND MODE

OUTPUTS

OUTPUTS

4 - 1

4 - 1

10 - 12

10 - 12

5 - 1

5 - 1

11 - 12

11 - 12

SETTING OF DIP-SWITCH SW2

SETTING OF DIP-SWITCH SW2

6 - 1

6 - 1

7 - 1

7 - 1

8 - 1

8 - 1

9 - 1

9 - 1

Meaning

Meaning

Meaning

Meaning

IN 1

Local / Remote

OUT 1

Alarm

IN 2

Start (*)

OUT 2

Start

IN 3

Stop (*)

IN 4

Thermal protection

IN 5

Feedback

IN 6

Silence alarm

Type

Type

Type

Type

N.O.

N.O.

N.D. (**)

N.E. (**)

N.O.

N.O.

N.D. (**)

N.D. (**)

N.O.

N.C.

N.O.

N.C.

N.O.

N.O.

N.O.

N.O.

1

2

3

4

ON

1

2

3

4

ON

Terminal

PNEUMATIC VALVE COMMAND MODE

OUTPUTS

10 - 12
11 - 12

SETTING OF DIP-SWITCH SW2

Meaning

Alarm
Start

Type

N.E. (**)
N.D. (**)

Terminal

INPUTS

4 - 1

5 - 1

6 - 1

7 - 1

8 - 1

9 - 1

Meaning

Local / Remote

Activation (*)

Return (*)

Return Travel-Limit

Activation Travel-Limit

Silence alarm

Type

N.O.

N.O.

N.C.

C.I.P.(***)

C.I.P.(***)

N.O.

1

2

3

4

ON

Module configuration (DIP-Switch SW2)

- I/O 
     
- MOTOR COMMAND MODE
     
- PNEUMATIC VALVE COMMAND MODE
     
- MOTORISED VALVE COMMAND MODE

MODE

To  start  the  motor,  close  the  "START"  input.  The  module  controls  if  the  "THERMAL 
PROTECTION"  and  "STOP"  inputs  are  closed  -  in  this  situation  it  enables  the  "START" 
output.
After the programmed time (see DIP-switches SW2-3 and 4 and modbus 40005 register) the 
closure of the “FEEDBACK” input is verified. If still open, the module enables the "ALARM" 
output (the "START" output remains enabled).  
If  the  "THERMAL  PROTECTION"  input  opens  during  operation,  the  "ALARM"  output  is 
immediately enabled, and the "START" output is disabled.
To silence the alarm, close the "SILENCE ALARM" input.
To stop the motor, open the"STOP" input - the module disables the "START" output.
The  "FEEDBACK"  input  must  open  within  the  programmed  time,  otherwise  the  module 
enables the "ALARM" output.

Terminal

MOTORISED VALVE COMMAND MODE

OUTPUTS

10 - 12

11 - 12

SETTING OF DIP-SWITCH SW2

Meaning

Return

Start

Type

N.D. (**)

N.D. (**)

Terminal

INPUTS

4 - 1

5 - 1

6 - 1

7 - 1
8 - 1

9 - 1

Meaning

Local / Remote

Activation (*)

Return (*)

Return Travel-Limit
Activation Travel-Limit

Not used

Type

N.O.

N.O.

N.C.

C.I.P.(***)
C.I.P.(***)

N.O.

1

2

3

4

ON

( * ) These commands are effective only if the Local / Remote input is in Local position 
(open contact). If the Local / Remote input is in Remote position (closed contact), the 
respective commands are sent to the module by writing in the  respective registers.

( ** ) N.D. = Normally de-energised relay N.E. = Normally energised relay.
( *** ) CIP = Closed in position

MOTORS COMMAND LOGIC (in LOCAL mode)

PNEUMATIC VALVE COMMAND LOGIC                 

     (in LOCAL mode )

To enable the pneumatic valve, close the "ACTIVATION" input. The module controls if the 
"RETURN"  input is closed - in this situation it enables the "ACTIVATION" output.
After the programmed time (see DIP-switches SW2-3 and 4 and modbus 40006 register), the 
opening of the "ACTIVATION TRAVEL-LIMIT" input is verified. If it is still closed, the module 
enables the "ALARM"  output (the "ACTIVATION " output remains enabled).
To silence the alarm, close the "SILENCE ALARM" input.
If you open the "RETURN" input, the module disables the "START " output.
The "RETURN TRAVEL-LIMIT" input must open within the programmed time, otherwise the 
module enables the "ALARM" output.
An incongruous situation of the travel-limit devices (simultaneous opening of the two inputs 
"ACTIVATION TRAVEL-LIMIT" and "RETURN TRAVEL-LIMIT") immediately activates the 
"ALARM" output and lights up the "FAIL" LED..

ENGLISH 8/13

MI000944-I-E

RS485 GND 

RS485 A 

RS485 B 

Power Supply AC + 

Power Supply AC- 

IDC 10 

Bus lenght

Drop lenght

1200 m

2 m

DIP SWITCH STATUS

POSITION

POSITION

From EEprom

BAUD RATE

xx000000

POSITION ADDRESS

xx000000

From EEprom

POSITION ADDRESS

01xxxxxx

11xxxxxx

10xxxxxx

19200

57600

38400

xx000010

xx111111

      .....   

     # 2

     # 63

     .....  

POSITION

TERMINATOR

BAUD RATE

00xxxxxx

9600

xx000001     # 1

none

    See J4

none

    See J4

Z-D-IO

Load

Load

Dout1

Dout2

Common

Содержание Z-PC SERIES

Страница 1: ... con comune portata 2 A 250 Vac AC1 Jumper interni per selezionare per ciascun relè il contatto N A o N C ALIMENTAZIONE CONDIZIONI AMBIENTALI Tensione Assorbimento 10 40 VDC 19 28 VAC a 50 60 Hz Tipico 1 5 W Max 2 5 W Temperatura Umidità Altitudine 10 65 C 30 90 a 40 C non condensante Fino a 2000 m s l m MI000944 I E MI000944 I E MI000944 I E MI000944 I E MI000944 I E MI000944 I E Manuale di Insta...

Страница 2: ...a smaltito in modo adeguato eviterete un potenziale impatto negativosull ambiente e la salute umana che potrebbe essere causato da una gestione non conforme dello smaltimento del prodotto Il riciclaggio dei materiali contribuirà alla conservazione delle risorse naturali Per ricevere ulteriori informazioni più dettagliate Vi invitiamo a contattare l ufficio preposto nella Vostra città il servizio p...

Страница 3: ...S 2 RELAY OUTPUTS MODBUS COMMUNICATION ON RS485 Contents General characteristics Technical specifications Installation rules Electrical connections Digital inputs Digital outputs DIP switch settings Modbus connections rules Module configuration Alarm delay DIP Switch SW2 3 e SW2 4 Logical schemes LEDs Signallings Factory settings Installation Manual Installation Manual Technical specifications INP...

Страница 4: ...ing stucture S Q T Z D IO PNEUMATIC VALVE LOGIC Activation Return Silence Alarm F C A F C R R 14 R 15 R 13 R 0 R 10 R 11 R 12 R 6 R 8 R 7 Activation Return S R Q R Pr Q T S Reset Loc Rem Note The register R 1 does not have effect The input Silence Alarm does not have effect Register 40002 Status of inputs and outputs Most significant bit R15 Least significant bit R0 The symbols R 15 R 0 represent ...

Отзывы: