USER MANUAL
–
Z-D-IN
14
6.
LEDs for signalling
In the front-side panel there are 9 LEDs and their state refers to important operating conditions of the
module.
LED
LED status
Meaning
PWR
Constant light
The power is on
ERR
Blinking light
The module has at least one of the errors/overflows described in
RS485 Registers table
Constant light
Module failure
RX
Constant light
Verify if the bus connection is corrected
Blinking light
The module received a data packet
TX
Blinking light
The module sent a data packet
Constant light
Verify if the bus connection is corrected
1-5
Constant light
IN1-5 state equal to «1»
No light
IN1-5 state equal to «0» (if the power is on)
7.
Filter
LPF1 action: Input filter
Cut-off frequency equal to 100Hz for
IN1-5
LPF2 action: Filter 1-254
Cut-off frequency range to attenuate
lower-frequencies noise: from 4Hz to
1kHz. The noise is overlapped to the
desired digital signal.