background image

ENGLISH

- 3/8

t

Power supply

RS485

MODBUS

Communicat.

1500 V

A

12

11

10

9

8

7

5

6

2

4
3

1

Input

TC

IDC10

IDC10

Input

TC

Input

TC

Input

TC

16

15

14

13

STANDARDS

EN61000-6-4

Electromagnetic emission, industrial environment
Electromagnetic immunity,  industrial environment

EN61000-6-2

Safety

EN61010-1

INSULATION

ENVIRONMENTAL COND.

Temp ratur

e

e

Hu

y

midit

Altitude
S rage temperature

to

P

ction degree

rote

-20 – +65°C.

EEPROM storing guaranteed in the range: 0    50 °C.

30% –

t condensing

90% no

Up to 2000 m a.s.l.
-20    + 85°C

20

IP

MOUNTING

IEC EN60715 DIN Rail

CONNECTIONS

Removable   -way terminals

4

,       mm

3.5

pitch, for cable max. 1.5mm .

2

Rear IDC10 connector for CEI EN60715 rail

Micro USB frontal panel connector.

POWER SUPPLY

Tension
Power absorbed

10 – 40 V

or 19 – 28 V

dc

ac

50    60 Hz

Max. 0.6W

COMMUNICATION
PORTS

RS485 on IDC10 rear connector.

PROTOCOLS

MODBUS-RTU.

TC INPUTS

Number of channels

Thermocouple

type: J, K, E, N, S, R, B, T.

8

TECHNICAL SPECIFICATIONS

LED

State

LEDs Meaning

PWR

(Green)

On

Power supply presence

Off

The device is powered off

FAIL

(Yellow)

On

Fault or Failure: power supply lack, failed channel, failed
T

, internal communication error.

hermocouple

RX (Red)

On

Data reception from

485 communication port.

RS

TX (Red)

On

Data transmission to

485 communication port.

RS

LED SIGNALLING ON FRONT PANEL

Содержание Z-8TC-LAB

Страница 1: ...8 ThermoCouple Inputs ENGLISH 8 1 THE ORIGINAL VERSION IS IN ITALIAN LANGUAGE This document is property of SENECA rl Duplication and reproduction are forbidden if not authorized S Contents of the pres...

Страница 2: ...rial communication with MODBUS RTU protocol l Frontal USB Port for MODBUS RTU con guration and communication l Channels individually activabl and con gurable in pairs e For the two inputs of each term...

Страница 3: ...l CONNECTIONS Removable way terminals 4 mm 3 5 pitch for cable max 1 5mm 2 Rear IDC10 connector for CEI EN60715 rail Micro USB frontal panel connector POWER SUPPLY Tension Power absorbed 10 40 V or 19...

Страница 4: ...sources PRELIMINARY WARNINGS TC type Allowed Range Linearization error TC type Allowed Range Lineariz error J 210 1200 C 0 05 C S 50 1768 C 0 02 C K 200 1372 C 0 05 C R 50 1768 C 0 02 C E 200 1000 C 0...

Страница 5: ...ide of the IDC10 rear connector as shown in Pic 1 Removal from IEC EN 60715 DIN rail As shown in Pic 2 1 Move outwards the two hooks on the side of the module with the help of a screwdriver 2 Extract...

Страница 6: ...e module will be inserted on a free slot of Z PC DIN accessory In the figure you can see the meaning of the various pins of the rear IDC10 connector if you want to provide the signals directly through...

Страница 7: ...the Internet site www seneca com Some parameters can also be set using DIP switches CONFIGURATIONS Detailed information about list of MODBUS registers and their functions are available inside the Z 8...

Страница 8: ...on Rejection ADC Filter Thermocouple type Both channels are enabled C Enabled 50 Hz ADC 15 bit with average filter J for both channels FACTORY SETTINGS DIP SWITCHES CONFIGURATION BAUD RATE SW1 1 2 960...

Отзывы: