background image

MI00362-4-EN

INSTALLATION MANUAL

4/4

ELECTRICAL CONNECTIONS

Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or the 

Z-PC-DINAL-17.5 accessory.

RS485 GND

 

RS485 A

 

RS485 B

 

Power Supply AC / +

 

Power Supply  AC / -

IDC 10

Back connector (IDC 10)

The illustration shows the meanings of the various 

IDC10 connector pins if signals are to be sent via 

them directly.

INPUTS

A) Voltage input with sensor supply from the MODULE (13 Vdc)

B) Voltage input with sensor supply NOT coming from the MODULE
C) Current input with sensor supply NOT coming from the MODULE

D) Current input with sensor supply from the MODULE (13 Vdc)
E) Current input with sensor EXTERNAL power supply 

#I 7

n

#I 5

n

#I 6

n

#I 8

n

#I 2

n

#I 4

n

#I 3

n

g n d

#I 1

n

g n d

+

+

+

+

T X

T X

T X

T X

v ext

T X

T X

T X

T X

+

A

B

C

D

E

S

S

S

S

+

+

+

+

T X

T X

T X

T X

v ext

T X

T X

T X

T X

+

S

S

S

S

vaux*

v aux

vaux

vaux

v aux

vaux*( generata dal modulo ) = 13 Vdc     

vaux*

The upper power supply limits must not be exceeded, as this might cause serious damage to the module. Switch 

the module off before connecting inputs and outputs. 

To meet the electromagnetic immunity requirements:

• 

use shielded signal cables;

• 

connect the shield to a preferential instrumentation earth system;

•  separate shielded cables from other cables used for power installations (inverters, motors, induction ovens, 

etc...).

• 

install a fuse with a MAX capacity of 2.5A near the module.

• 

make sure that the power supply voltage to the module does not exceed: 40Vdc or 28Vac, otherwise the mod

-

ule will be damaged.