MI00562-2-EN

INSTALLATION MANUAL

3/4

STANDARDS

EN61000-6-4

  Electromagnetic emissions, industrial environment.

EN61000-6-2

 

Electromagnetic immunity, industrial environment.

EN61010-1 

Safety.

INSULATION

Using an insulated conductor, its sheath determines the insulation voltage.

An insulation of 3 kV ac is guaranteed on bare conductors.

ENVIRONMENTAL 

CONDITIONS

Temperature

-25 ÷ +65 °C

 

Humidity

10% ÷ 90% non condensing.

Altitude: 

Up to 2000 m above sea level

 

Storage temperature:

 

-30 ÷ +85°C

 

Degree of protection: 

IP20.

ASSEMBLY

35mm DIN rail IEC EN60715, suspended with ties

CONNECTIONS

Removable 6-way screw terminals, 5 mm pitch for cable up to 2.5 mm

2

micro USB

POWER SUPPLY

Voltage: on Vcc and GND terminals, 11 ÷ 28 Vdc;

Absorption: Typical: < 70 mA @ 24 Vdc

COMMUNICATION 

PORT

RS485 serial port on terminal block with ModBUS protocol (see user manual)

INPUT

Type of measurement

: AC/DC TRMS or DC Bipolar

Live: 1000Vdc; 290Vac

Crest factor

: 100A = 1.7 ; 300A = 1.9 ; 600A = 1.9

Pass-band: 

1.4 kHz

Overload: 

3 x IN continuous

CAPACITY

AC/DC True RMS

TRMS DC Bipolar (DIP7=ON)

T203PM600-MU

0 – 600A / 0 – 290Vac

-600 – +600A / 0 – +1000Vdc

T203PM300-MU

0 – 300A / 0 – 290Vac

-300 – +300A / 0 – +1000Vdc

T203PM100-MU

0 – 100A / 0 – 290Vac

-100 – +100A / 0 – +1000Vdc

ANALOGUE 

OUTPUT

Type

0 – 10 Vdc, minimum load R

LOAD

 =2 kΩ.

Protection

Reverse polarity protection and over voltage protection

Resolution: 

13.5 full scale AC

EMI error: 

< 1 %

The type of output can be selected via software

DIGITAL 

OUTPUT

Type

: active, 0 – Vcc, maximum load 50mA

The type of output can be selected via software

ACCURACY

below 5% of full scale

1% of full scale at 50/60 Hz, 23°C

above 5% of full scale

0,5% of full scale at 50/60 Hz, 23°C

Coeffic. Temperature

< 200 ppm/°C

Hysteresis on measurement

:  0.3% of full scale

Response speed: 

500 ms (DC); 1 s (AC) al 99,5%

OVERVOLTAGE 

CATEGORIES

Bare conductor: 

CAT. III 600V

Insulated conductor: 

CAT. III 1kV

TECHNICAL SPECIFICATIONS

Содержание T203PM100-MU

Страница 1: ...opriate measures during any operation PRELIMINARY WARNINGS The word WARNING preceded by the symbol indicates conditions or actions that put the user s safety at risk The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment The warranty shall become null and void in the event of improper use or tampering with the module or...

Страница 2: ... the magnetic field possibly if the zero error is greater than the declared error try a different arrangement or change orientation CAUTION USB PORT The front USB port allows easy connection to configure the device using the configuration software If it is necessary to restore the initial configuration of the instrument use the configuration software Through the USB port it is possible to update t...

Страница 3: ...er manual INPUT Type of measurement AC DC TRMS or DC Bipolar Live 1000Vdc 290Vac Crest factor 100A 1 7 300A 1 9 600A 1 9 Pass band 1 4 kHz Overload 3 x IN continuous CAPACITY AC DC True RMS TRMS DC Bipolar DIP7 ON T203PM600 MU 0 600A 0 290Vac 600 600A 0 1000Vdc T203PM300 MU 0 300A 0 290Vac 300 300A 0 1000Vdc T203PM100 MU 0 100A 0 290Vac 100 100A 0 1000Vdc ANALOGUE OUTPUT Type 0 10 Vdc minimum load...

Страница 4: ...GUE OUTPUT DIGITAL OUTPUT Connect just a pair of terminals for the measurement ELECTRICAL CONNECTIONS CAUTION Switch off the module before connecting the inputs and outputs To meet electromagnetic immunity requirements use properly insulated and dimensioned cables use shielded cables for signals connect the shield to a preferred instrumentation ground Keep shielded cables away from other cables us...

Отзывы: