MI00562-2-EN
INSTALLATION MANUAL
3/4
STANDARDS
EN61000-6-4
Electromagnetic emissions, industrial environment.
EN61000-6-2
Electromagnetic immunity, industrial environment.
EN61010-1
Safety.
INSULATION
Using an insulated conductor, its sheath determines the insulation voltage.
An insulation of 3 kV ac is guaranteed on bare conductors.
ENVIRONMENTAL
CONDITIONS
Temperature
:
-25 ÷ +65 °C
Humidity
:
10% ÷ 90% non condensing.
Altitude:
Up to 2000 m above sea level
Storage temperature:
-30 ÷ +85°C
Degree of protection:
IP20.
ASSEMBLY
35mm DIN rail IEC EN60715, suspended with ties
CONNECTIONS
Removable 6-way screw terminals, 5 mm pitch for cable up to 2.5 mm
2
micro USB
POWER SUPPLY
Voltage: on Vcc and GND terminals, 11 ÷ 28 Vdc;
Absorption: Typical: < 70 mA @ 24 Vdc
COMMUNICATION
PORT
RS485 serial port on terminal block with ModBUS protocol (see user manual)
INPUT
Type of measurement
: AC/DC TRMS or DC Bipolar
Live: 1000Vdc; 290Vac
Crest factor
: 100A = 1.7 ; 300A = 1.9 ; 600A = 1.9
Pass-band:
1.4 kHz
Overload:
3 x IN continuous
CAPACITY
AC/DC True RMS
TRMS DC Bipolar (DIP7=ON)
T203PM600-MU
0 – 600A / 0 – 290Vac
-600 – +600A / 0 – +1000Vdc
T203PM300-MU
0 – 300A / 0 – 290Vac
-300 – +300A / 0 – +1000Vdc
T203PM100-MU
0 – 100A / 0 – 290Vac
-100 – +100A / 0 – +1000Vdc
ANALOGUE
OUTPUT
Type
:
0 – 10 Vdc, minimum load R
LOAD
=2 kΩ.
Protection
:
Reverse polarity protection and over voltage protection
Resolution:
13.5 full scale AC
EMI error:
< 1 %
The type of output can be selected via software
DIGITAL
OUTPUT
Type
: active, 0 – Vcc, maximum load 50mA
The type of output can be selected via software
ACCURACY
below 5% of full scale
1% of full scale at 50/60 Hz, 23°C
above 5% of full scale
0,5% of full scale at 50/60 Hz, 23°C
Coeffic. Temperature
:
< 200 ppm/°C
Hysteresis on measurement
: 0.3% of full scale
Response speed:
500 ms (DC); 1 s (AC) al 99,5%
OVERVOLTAGE
CATEGORIES
Bare conductor:
CAT. III 600V
Insulated conductor:
CAT. III 1kV
TECHNICAL SPECIFICATIONS