MI00562-2-EN

INSTALLATION MANUAL

2/4

Dimensions LxHxD

 95 x 75 x 35 mm; 

Weight:

 ≈ 150 g; 

Enclosure:

 PA6, black

LED

STATUS

LED meaning

PWR/COM Green

ON

The device is powered correctly

PWR/COM Green

Flashing

Communication via RS485 port

D-OUT Yellow

ON

Digital output activated

ASSEMBLY

The device can be mounted in any position, in compliance with the expected environmental conditions.

Magnetic fields of considerable magnitude can alter the measurement: avoid proximity to permanent magnetic fields, 

solenoids or ferrous masses which induce strong alterations of the magnetic field; possibly, if the zero error is greater than 

the declared error, try a different arrangement or change orientation.

CAUTION

USB PORT

The  front  USB  port  allows  easy  connection  to  configure  the  device  using  the  configuration  software. 

If  it  is  necessary  to  restore  the  initial  configuration  of  the  instrument,  use  the  configuration  software.

 

Through the USB port it is possible to update the firmware (for further information please refer to the Easy Setup 2 

software).

MODULE LAYOUT

SIGNALS VIA LED ON FRONT PANEL

35 mm

CU

MICROOTG

-A

CU

MICROB

-A-

CU

MICROB

-A-

Configurazione

tramite APP

Android

Configurazione

tramite

software PC

Check that the device in question is included in the list of products supported by the Easy Setup APP in the store.

Содержание T203PM100-MU

Страница 1: ...opriate measures during any operation PRELIMINARY WARNINGS The word WARNING preceded by the symbol indicates conditions or actions that put the user s safety at risk The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment The warranty shall become null and void in the event of improper use or tampering with the module or...

Страница 2: ... the magnetic field possibly if the zero error is greater than the declared error try a different arrangement or change orientation CAUTION USB PORT The front USB port allows easy connection to configure the device using the configuration software If it is necessary to restore the initial configuration of the instrument use the configuration software Through the USB port it is possible to update t...

Страница 3: ...er manual INPUT Type of measurement AC DC TRMS or DC Bipolar Live 1000Vdc 290Vac Crest factor 100A 1 7 300A 1 9 600A 1 9 Pass band 1 4 kHz Overload 3 x IN continuous CAPACITY AC DC True RMS TRMS DC Bipolar DIP7 ON T203PM600 MU 0 600A 0 290Vac 600 600A 0 1000Vdc T203PM300 MU 0 300A 0 290Vac 300 300A 0 1000Vdc T203PM100 MU 0 100A 0 290Vac 100 100A 0 1000Vdc ANALOGUE OUTPUT Type 0 10 Vdc minimum load...

Страница 4: ...GUE OUTPUT DIGITAL OUTPUT Connect just a pair of terminals for the measurement ELECTRICAL CONNECTIONS CAUTION Switch off the module before connecting the inputs and outputs To meet electromagnetic immunity requirements use properly insulated and dimensioned cables use shielded cables for signals connect the shield to a preferred instrumentation ground Keep shielded cables away from other cables us...

Отзывы: