REGISTER
NAME
COMMENT
REGISTE
R TYPE R/W
DEFAUL
T VALUE
OR
START
VALUE
ADDRESS
(4xxxx)
OFFSET
ADDRES
S
ALARM TYPE
Select the Alarm linked
to the Digital Output:
0 = NONE
1 = MAX (Alarm if the
Current is above the
High Threshold)
2 = MIN (Alarm if the
Current is below the Low
Threshold)
3 = Window INT (Alarm
if the Current > Low
Threshold but < High
Threshold)
4 = Window EXT (Alarm
if the Current is > High
Threshold or < Low
Threshold)
Unsigned
16 bits
RW*
0
40108
107
DOUT MODE
0 = Digital Output is
normally Low
1 = Digital Output is
normally High
Unsigned
16 bits
RW*
0
40109
108
ALARM
DELAY
Alarm delay in x 10ms
(for example write
1000
for obtain 10 seconds of
delay)
Unsigned
16 bits
RW*
0
40110
109
START INPUT
SCALE
Select the Start Input
Scale [A]
Float32
RW*
According
to the
model
40111 (LSW)
40112 (MSW) 110-111
STOP INPUT
SCALE
Select the Stop Input
Scale [A]
Float32
RW*
According
to the
model
40113 (LSW)
40114 (MSW) 112-113
START
OUTPUT
SCALE
Select the Start output
Scale [V]
Float32
RW*
0.0 V
40115 (LSW)
40116 (MSW) 114-115
STOP
OUTPUT
SCALE
Select the Stop output
Scale [V]
Float32
RW*
10.0 V
40117 (LSW)
40118 (MSW) 116-117
ALARM
HYSTERESIS
Select the Hysteresis for
the Alarm in [A]
Float32
RW*
10.0 A
40119 (LSW)
40120 (MSW) 118-119