TECHNICAL SPECIFICATIONS

STANDARDS

EN61000-6-4

 

Electromagnetic emissions, industrial environment.

EN61000-6-2

 

Electromagnetic immunity, industrial environment.

EN61010-1 

Safety

Install a fuse with a maximum capacity of 1 A near the module.

ENVIRONMENTAL

CONDITIONS

Temperature: 

-10 ÷ + 65°C

Humidity: 

30% ÷ 90% non condensing.

Storage temperature: 

-20    + 85°

Protection rating: 

IP65 (on the front with appropriate gasket)

INSULATION

2500 Vdc between each pair of ports (including those belonging to the optional board)

POWER SUPPLY

S311D-XX-L: 10 ÷ 40 Vdc, 19 ÷ 28 Vac, 50 ÷ 60 Hz, max. 3 W 

S311D-XX-H: 85 ÷ 265 Vac, 50 ÷ 60 Hz, max. 3 W

CONNECTIONS

Removable screw terminals, 3.5 mm/5.08 mm pitch

DIGITAL

INPUT

Type: Reed, Npn (2 wires), npn 24 V (3 wires) or pnp 24 V (3 wires), NAMUR, Photoelectric 

(Astra), Hall, 24 V input, TTL, Variable reluctance.

Absorbed current: max. 7 mA

Vmax.: 28 Vdc

Sensor power supply: 17 Vdc

Frequency band: 0.00014 Hz ÷ 10 kHz

Frequency resolution: < 0.05 %

ANALOGUE

OUTPUT

Applied current: 0 ÷ 20 mA, max. load resistance 500 W

Voltage: 0 ÷ 10 V, min. load resistance 1 kW

Configurable start and end of scale

Resolution: 2 mA / 1 mV

Response time: 5 ms

Maximum measurement field errors:

Calibration error: 0.1%

Thermal coefficient: 0.01%/°K

Linearity error: 0.05%

EMI (electromagnetic interference): < 1%

DIGITAL OUTPUT

Open Collector type, Imax: 50 mA, Vmax: 30 V

RELAY OUTPUT

Capacity: 8 A / 250 Vac (available only on optional board)

AUX. DIGITAL INPUT

Optoinsulated, Vmin: 10 V, Vmax: 30 V (available only on optional board)

OPERATION DESCRIPTION

The measurement of the digital input frequency or the totalizer value is translated into an analogue or digital output signal. 

The frequency value or alternatively the totalizer value can also be viewed via the display; in the 11-digit model (4 + 7) both 

values can be displayed simultaneously (4 digits: frequency value, 7 digits: totalizer value). The values are also available 

via MODBUS-RTU protocol from the RS485 port (via optional board). 

Setting mode:

All the parameters of the instrument can be set via the Programming Menu or RS485 (via optional board). The alarm 

thresholds can also be set quickly via the specific Quick Alarm Menu. The dedicated Easy Setup software for programming/

configuring the module was also developed (see www.seneca.it). 

Retransmission mode:

The instrument accepts the following retransmission modes:

Analogue output:

 The measurement of the frequency of the digital input is translated into an analogue output signal 

(current or voltage).

Digital output:

 The output generates an impulse every time the totalization is increased or decreased. A pulse of duration 

≥ ~ 100 ms is generated. The output follows the totalizer up to the maximum value of approximately 4.7 Hz. As the counting 

frequency increases (up to the maximum value shown above), pulses are gradually lost until an output is obtained always at 

a low logic level. The output is normally high.

Содержание S311D L Series

Страница 1: ...git display advanced digital totalizers indicators SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals in other languages and the configuration sof...

Страница 2: ...are not followed 96 mm 98 mm 48 mm WARNING The full content of this manual must be read before any operation The module must only be used by qualified electricians Specific documentation is available...

Страница 3: ...pacity 8 A 250 Vac available only on optional board AUX DIGITAL INPUT Optoinsulated Vmin 10 V Vmax 30 V available only on optional board OPERATION DESCRIPTION The measurement of the digital input freq...

Страница 4: ...nit at each rising edge of the digital input Decreasing it is decreased by one unit at each rising edge of the digital input Once the maximum or minimum limit is reached counting restarts from zero It...

Страница 5: ...l power supply for the sensors equal to 17 Vdc is available at terminals 7 and 10 03 04 05 06 VOLTAGE V 03 04 05 06 APPLIED CURRENT A Active output already powered to be connected to passive inputs 03...

Страница 6: ...imum value 0 Max value depending on the display 4 11 4 7 digits 9999 without decimal point 6 8 digits 10000 without decimal point 1000 Hz dpIn Position of decimal point in HI F 0 no decimal point e g...

Страница 7: ...on the minimum held threshold does not automatically reset 4 Alarm on the maximum held threshold does not automatically reset 5 Alarm on the totalizer threshold value does not automatically reset 0 N...

Страница 8: ...N digits display 1 For 11 digit models 4 7 max number of decimal places equal to 6 0 No decimal point e H I t Confirming with OK MENU you save all parameters on a flash card and after a few moments re...

Отзывы: