POWER SUPPLY

MeterBUS PORT

RS485 SERIAL PORT

RS232 SERIAL PORT

The power supply source must 

be protected from any module 

malfunctions using appropriately-sized 

safety fuses.

5/6

ELECTRICAL CONNECTIONS

10
11

Vac / Vdc
Vac / Vdc

MeterBUS
MeterBUS

A (+)
B (-)

GND

1
2

3
4
5

CONNECTION STANDARDS

MeterBUS is a non-polarized bus.

For the connection it is possible to use a two-wire shielded telephone cable or an unshielded duplex cable following the 

indications in the table.

If a shielded cable is used, this must be 

connected to earth only from the R-KEY-MBUS side.

Type of

installation

Maximum

speed

Connection

maximum distance

Connection

total length

Type of cable

Small in house

38400

< 350 m

< 1000 m

0.5 mm

2

, R < 30 Ω

Large in house

9600

< 350 m

< 3000 m

0.5 mm

2

, R < 30 Ω

Small wide area

2400

< 1000 m

< 3000 m

1.5 mm

2

, R < 90 Ω

5
6

8

9

7

GND
RTS

CTS
Rx

Tx

CAUTION

On first start-up the module must be supplied without any interruptions for at least 72 hours to charge the internal 

batteries. Switch the module off with the PS1 button before connecting inputs and outputs.

To meet the electromagnetic immunity requirements:

- use shielded signal cables;

- connect the shield to a preferential instrumentation earth system;

- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc...).