3/6
TECHNICAL SPECIFICATIONS
STANDARDS
EN61000-6-4
Electromagnetic emissions, industrial environment.
EN61000-6-2
Electromagnetic immunity, industrial environment.
EN60950-1
Safety.
POWER SUPPLY
Voltage: 11 – 40 Vdc, 19 - 28 Vac, 50 - 60 Hz; Absorption: Max p.: 3.8 W.
INSULATION
CONNECTIONS
Removable 2-way screw terminals, 5 mm pitch for cable up to 2.5 mm
2
RJ45 Ethernet connector
ENVIRONMENTAL CONDITIONS
Operating temperature:
from -25°C to +65°C
Humidity: 10%– 90% non condensing.
Storage temperature:
from -30°C to +85°C
Protection rating:
IP20
COMMUNICATION PORTS
RS232/RS485: on terminals;
Ethernet (RJ45): 100 Mbit/s, max. distance 100 m with auto switch
PROTOCOLS
MeterBUS, ModBUS TCP server and ModBUS RTU slave.
For more information see the
User Manual.
M-Bus PORT
on terminals 1 and 2 (see electrical diagrams)
Number of slaves: 25 Max.
Speed: 300 – 38k4 Baud
Voltage: 28 Vdc
Maximum length: 3000 m
CONFIGURATION
Configuration and FW update via webserver
DIP-switch
ASSEMBLY
On IEC EN60715 rail or wall fixing
Restart button:
The button is located between the SW1 DIP-switch and the Ethernet port.
To reboot the device, just
keep the button pressed for 5 seconds.
Release it when all the LEDs light up.
MeterBUS
RS485/RS232
Ethernet
POWER
SUPPLY
1500 Vdc
500 Vdc