Reset/Technical data
6. Technical data
Series
Torque
Nm
Rotation speed
Rpm
Power Input
A
Output
W
1/10
10
15
0.5
115
2/7
7
17
0.41
95
2/10
10
17
0.45
105
2/15
15
17
0.66
152
2/20
20
17
0.75
172
2/30
30
17
0.95
220
Series 2 motors have a plug-in connection cable. Series 1 and series 3 motors have a
2.5 m mains cable as standard which is permanently installed and
cannot
be
replaced.
The relevant cable lengths and qualities for series 2 can be selected in the catalogue.
Connection cables must be ordered separately.
Information about connections using special connectors must be requested.
Information for all motor types:
Nominal voltage: 230 V AC/50 Hz
Safety class:
IP 44
Operating time: 4 Min.
Subject to change without prior notice!
5. Reset
Precondition: Both end positions must be set, this means that the drive no longer
performs a short release when reaching the lower end position.
Reset with
switch
Reset with
setting switch
Drive
E
1 s
Connect the setting switch cable to the motor
wiring cable.
Press the
E
button of the setting switch for
1 second. Both limit positions already set will be
deleted.
Alternatively: Move the drive upwards until it stops
automatically at the upper limit stop and performs
a short release.
5x 3 s with
1 s pause
Then press the switch 5 times for 3 seconds with
1 second pause in upwards direction.
Then turn on the upward direction again. The drive
moves down and switches off automatically. Now
turn off the switch.