The input “dew point” enables the connection of digital or analogue dew point
sensor.
Parameter C1.7 is used to set the type of dew point sensor, which is connected to
the input “dew point”.
C1.7=0 - input is not used,
C1.7=1 - digital sensor of type NC (short circuit when dew point is detected),
C1.7=2 - digital sensor of type NO (open connection terminals when dew point is
detected),
C1.7=3 - analogue sensor (FCD dew sensor).
The sensor is mounted on the supply line. In case of detected dewing, the cooling
stops.