English
21
The condition for the activation of energy source and circulation pump is the de-
mand for heating or cooling in at least one zone.
Energy source settings:
Parameter C3.12 is used to set the energy source output switch-on delay.
Parameter C3.13 is used to set the energy source output switch-off delay.
Parameter C3.14 is used to set the energy source output operation:
C3.14=1 - normal operation (when the energy source is on, the output is under
operating voltage),
C3.14=2 - inverted operation (when the energy source is on, there is no operating
voltage at the output).
Circulation pump settings:
Parameter C3.2 is used to set the circulation pump output switch-on delay.
Parameter C3.3 is used to set the circulation pump output switch-off delay.
Parameter C3.4 is used to set the circulation pump output operation:
C3.4=1 - normal operation (when the circulation pump is on, the output is under
operating voltage),
C3.4=2 - inverted operation (when the circulation pump is on, there is no operating
voltage at the output).
Energy source and circulation pump (ZCE6 Advance)
Up to 6 RCD room units can be connected to the controller. Wire and wireless
room units can be connected. Wire units must connected to the connection termi-
nals with label “room units” (1, 2, 3, 4, 5, 6), and for the operation of wireless room
units, antenna must be connected to the terminal “ANTENNA”.
Each room unit represents one temperature zone and can affect one or more heat
-
ing zones. Establishing a connection between the controller and the room units
and determining the effect of the room unit on the zones is carried out by a pairing
process.
The pairing process is the same for wire and wireless room units.
The room unit exchanges the measured and desired values for its temperature
area with the controller:
- measured room temperature,
- measured air humidity,
- measured air pressure,
- desired daytime temperature,
- desired nighttime temperature,
- desired protection temperature,
- operating regime,
- user features ON/OFF.
Room units
Содержание ZCE6 Basic
Страница 1: ...Zone heating cooling controller ZCE6 Basic and ZCE6 Advance EN Instructions for use and setup...
Страница 27: ...English 27 CONTROLLER INSTALLATION 1 2 3 4...
Страница 30: ...30 English Hydraulic scheme 1 230V ZCE6 Basic and Advance HYDRAULIC SCHEMES...
Страница 31: ...English 31 Hydraulic scheme 1 24V ZCE6 Basic and Advance...
Страница 32: ...32 English Hydraulic scheme 2 230V ZCE6 Advance...
Страница 33: ...English 33 Hydraulic scheme 2 24V ZCE6 Advance...
Страница 34: ...34 English Hydraulic scheme 3 230V ZCE6 Advance...
Страница 35: ...English 35 Hydraulic scheme 3 24V ZCE6 Advance...