Bedienungsanleitung SDT43
BDA Serie SDT43 (Stand Jan. 2018)
Seite 47
SIMULATION
After linearization is entered and stored, it is possible to perform a simulation based on the
entered value’s. Based on the value entered in mWc, the transmitter will display the number of
hectoliters (on the basis of the specified linearization values).
6.
Navigate to program point
1.11 – TANK LIN,
and push the navigation button to enter the menu.
7.
Navigate to
Vert. Cone
. with the navigation button, and push to confirm.
8.
Two choices appear on the screen:
Input
and
Simulate
9.
Select
Simulate
, and push to confirm.
10.
Fill in the desired value based on mWc, the number of hectoliters change directly with a
change in the value mWc.
LINEARIZATION VERTICAL TANK WITH A
TRUNCATED BOTTOM
8.
Navigate to
Vert. Trunc
. with the navigation button, and push to confirm.
9.
Two choices appear on the screen:
Input
and
Simulate
10.
Select
Input
, and push to confirm.
11.
Six choices appear on the screen:
Display
Drawing
Explanation
Height1
H1
The height of the tank
Diameter 1
D1
The diameter of the tank
Height 2
H2
the height of the cone
Height 3
H3
The height till the topside of the diaphragm
Diameter 2
D2
The diameter of the truncated bottom
Fill Height
FH
The maximum percentage of filling of the tank
12.
Fill in each value, and confirm with the navigation button.
The entered value’s must be in meters.
13.
Select
to save the setting.
14.
The transmitter will return to the main menu
SIMULATION
D2
D1