www.selectronix.us
Selectronix, Inc.
(425) 788-2979
SLC4075 TouchScreen Gateway Installation & Operating Manual
___________________________________________________________________________________________________
20
SLC4000 Information
a.
Qty Sys Rlys
is the quantity of relays on all SLC4000 units.
b.
S4K Ver:
displays the firmware version of the SLC4000 master
c.
Sys Rlys On
is the quantity of system relays activated.
d.
Ld Lmt Rlys
is the quantity of relays that can be energized after the load limit has been applied.
e.
Aux Step Cmd %
is the local command percent connected to the master SLC4000.
f.
DDC Step Cmd %
is the DDC command percent sent via SLCnet to the master SLC4000.
g.
S4K Ld Lmt %
is the local load limit percent connected to the master SLC4000.
h.
DDC Ld Lmt %
is the DDC load limit percent sent via SLCnet to the master SLC4000.
i.
S4K OnDly Secs
is the setting of the On Delay on the master SLC4000 unit.
j.
DDC OnDly Secs
is the setting of the On Delay sent via SLCnet to the master SLC4000 unit.
k.
S4K Vnr Out %
is the percent of the 0-10 V dc vernier output.
l.
Command Status Table prior to V5.15
S4K Src
PGW Src
TSGW Src
DDC Dis or blank
DDC En or blank
DDC En or blank
Rlys On shows system relays on
Cmd if originates Step Cmd or blank Cmd if originates Step Cmd or blank
blank
LdLmt if originates Ld Lmt or blank
LdLmt if originates Ld Lmt or blank
a.
V5.15+ The Command Status Table is replaced with the following:
a.
S4K[0] Pct Out
is the percent output of the Master S4K.
b.
S4K[1] Pct Out
is the percent output of the Exp01 S4K.
c.
S4K[2] Pct Out
is the percent output of the Exp02 S4K.
d.
S4K[3] Pct Out
is the percent output of the Exp03 S4K.
b.
S4K Fault
: displays the SLC4000 fault code
HMI Information
a.
HMI Model:
Model of the TSGW HMI
b.
HMI Runtime Ver:
Runtime version of the HMI
c.
HMI Config Ver:
Configuration version of the HMI
d.
HMI Bootloader Ver:
Bootloader version of the HMI
User Manager
The Selectronix Building Management Interface allows remote write access to various data points via BACnet or
Modbus. It is the end-user’s responsibility to determine which data points are allowed to be changed, and which user
may perform this action. Red Lion’s Crimson software provides comprehensive security features to qualify user’s
access. Refer to the Crimson User’s manual available at www.redlion.net.
Provides for the authenticated access to the pre-defined protected pages or data points.
a.
Configured using the Crimson 3 software. See section “Using The Security System”
b.
Of particular importance is the Edit Access Control Dialog,