background image

Resolution: 1

Resolution: 0.1

RANGE

INPUT TYPE

UNIT

FUNCTIONS

To view Level 1

To view Level 2

To view Protection Level

KEY PRESS

Press     key for 3 sec. 

Press     key for 3 sec. 

Press     +     keys for 3 sec. 

FRONT KEYS DESCRIPTION

ONLINE

To view online 
parameters

PROGRAMMING MODE

To change online 
parameter values

Press     +     /     to change
parameter value. 

Lower display selectable between 
SET1/SET2/TIME

 

using 

   

 key. 

 

To view parameters on 
the same level. 

To increase or decrease 
the value of a particular 
parameter.

     or     key once to view the next or 
previous function in operational menu.

 

  

  +  

  

 to increase and  

  

  +  

  

to 

decrease the function value.

Note : 

Parameter value will not alter

when respective level is locked.

NOTE : The unit will auto exit programming mode after 30 sec. 
             of inactivity. 

By pressing the       or       or       +       keys for 3 sec.

OR

NOTE :

 Elapsed time

 

/

 

Remaining time dependent on the 

             

selection

 

of ONL parameter in level1. 

1

Process-value (PV) /
Parameter name 
display

1) Displays a process value (PV).
2) Displays the parameter symbols 
    at configuration mode/online menu.
3) Displays PV error conditions. 
    

(refer Table 2)

FRONT PANEL DESCRIPTION

4

3

1

2

1

T

2

5

S

6

5

Tune

6

Dwell timer

Auto tune : Blinking (With faster rate) 
Self tune : Blinking (With slower rate) 

Blinking : Dwell timer is in progress.
Continuous ON : Time over.

3

Control output 1 
indication

2

Parameter setting
display

The LED is glow when the control 
output 1 is ON

Displays the parameter settings at 
configuration mode/online menu.

4

Control output 2 
indication

The LED is glow when the control 
output 2 is ON

FOR THERMOCOUPLE

J

-199 to 750

°

C

When an error has occurred, the upper display indicates error 
codes as given below.

Error

Sensor break / 
Over range condition

Sensor reverse / 
Under range condition

OFF

OFF

Description

Control Output 

Status

Table 2 : ERROR DISPLAY 

T

R, S

If upper display is selected as           /      then,
Pressing   

 

key will show on 

 

Upper display

 

:

           

                                               Lower display: <0>
Press     +     /     keys to increment / decrement
           /      value. 

If upper display is selected as            then,
Pressing     key will show on Upper display : 

                                              

Lower display

  

  

<50>

Press     +    /     keys to increment / decrement              
value.  

 Range : SPLL to SPHL

Default : 50 

Programming online parameters

Setpoint 1

 Range : SPLL to SPHL

Setpoint 2 / Dead band

Default : 0 

If upper display is selected as             /            then,  
Pressing     key will show on Upper display : 
                                              Lower display : <OFF>
Press     +     /     keys to increment / decrement
            time value.

 Range : OFF, 1 to 9999 min

Dwell Timer

Default : OFF 

Use only the correct thermocouple wire or 
compensating cable from the probe to instrument 
terminals avoiding joints in the cable if possible. 
Failure to use the correct wire type will lead to 
inaccurate readings.
Ensure that the input sensor connected at the 
terminals and the input type set in the temperature 
controller configuration are the same. 

USER GUIDE

USER GUIDE

1. Display Bias :

 This function is used to adjust the PV

value in cases where it is necessary for PV value to agree
with another recorder or indicator, or when the sensor
cannot be mounted in correct location.

2. Filter Time Constant : 

The input filter is used to filter out

quick changes that occur to the process variable in a
dynamic or quick responding application which causes
erratic control.

The digital filter also aids in controlling processes where 

the electrical noise affects the input signal.

Larger the value of FTC entered, greater the filter added 

and the slower the controller reacts to the process and
vice versa.

3. Auto tune (AT) :

 The Auto-tuning function automatically

computes and sets the proportional band (P), 
integral time (I), Derivative time (D), ARW% and 
cycle time (CY.T) as per process characteristics.

Tune LED blinks at faster rate when auto-tuning is in
progress.
At the completion of Auto-tuning, Tune LED stops
blinking. 

If the power goes OFF before auto-tuning is completed,
Auto-tuning will be restarted at next power ON.

!

!

!

Temp.

set point

Proportional  band

PID - time proportioning with auto reset & rate

Time

AT off

!

!
!

  Self-tuning is initiated under the following conditions :

1) When setpoint is altered.
2) When tune mode is altered. (TUNE=ST)
ST will start only if PV < 50% of setpoint. 
ST will work only when ACT=RE.

6. Self Tune (ST) :  

It is used where modification of PID 

parameters is required repeatedly due to frequent 
change in process condition eg. Setpoint. 

Tune LED blinks at slower rate when Self-tuning is in 
progress.
At the completion of self-tuning, Tune LED stop 
blinking.

!

!

Time

Set point

Temp.

Proportional band

Reduced overshoot

5. Manual Reset (for PID control & I = 0) : 

After some 

time the process temperature settles at some point 
and there is a difference between the set temperature 
& the controlled temperature. This difference can be 
removed by setting the manual reset value equal & 
opposite to the offset. 

!

!

If auto-tuning is not completed after 3-4 cycles, the auto-
tuning is suspected to fail. In this case, check the wiring 
& parameters such as the control action, input type, etc.
Carry out the auto-tuning again, if there is a change in 
setpoint or process parameters. 

4. ON/OFF control action (For Reverse Mode) :

 

The  relay  is  ‘ON’  up  to  the  set  temperature  and  cuts 
‘OFF' above the set temperature. As the temperature of 
the system drops, the relay is switched ‘ON' at a
temperature slightly lower than the set point.

    HYSTERESIS :

 

The difference between the temperature at which 
relay switches ‘ON’ and at which the relay switches 
‘OFF’ is the hysteresis or dead band.

set point

Temp.

Offset

Manual reset 

adjusted

Time Proportional With Manual Reset

Time

set point

overshoot

Hysteresis

ON     

  ON

OFF

Output

Temp.

Time

Reverse 

set point

Hysteresis

OFF    

ON  

OFF

Temp.

Time

Output

Forward

Table 1 : INPUT RANGE

Resolution: 1

Resolution: 0.1

-238 to 1562

-199.9 to 999.9

RANGE

PT100

FOR RTD 

INPUT TYPE

°F

-150 to 850

-150.0 to 850.0

°

C

UNIT

-199 to 1350

-199 to 400

0 to 1750

-199 to 999

-199 to 400

N/A

-328 to 2462

-328 to 750

32 to 3182

-199 to 999

-199 to 750

N/A

°

C

°

C

°

C

°F

°F

°F

-328 to 1382

-199 to 999

°F

K

-199 to 750

TC544

 
Doc. Name : OP INST TC544C                  OP723-V03(Page 2 of 4)

7. Thermocouple Compensation :

 

COMP = YES

Configure Yes if compensating cable is connected

 

as

thermocouple extension. Yes should also be configured 
in the case if the sensor is directly connected to the
terminal without extension.

COMP = NO

Configure No if non-compensating cable is connected 
as thermocouple extension.

IDM Level 

IndependentDownloader Module

Upload from product to IDM 

Download te Parameter

Display

 Parameter Description

Download from IDM to product

Operation Successful

Operation unsuccessful 

Key

Key

+      Key

+      Key

/

/

Key

Key

Key

Key

(Blinking)

(Blinking)

Note:

 

1) IDM Level - IDM should be connected before
    powering on the unit to enter in IDM Level.
2) Long Press     or     key for 3 sec to exit from IDM mode.

Caution:

 After Downloading, switch of the unit and then remove the IDM

**IDM is applicable only for IDM compatible Product.