User Manual M8100 

M8196-72E 

 

Page 6 of 7 

5

 

Specifications 

Max. Voltage 

 

660V 

Voltage range 

 

70 - 110% 

Consumption  

 

2x 3VA max. 

Frequency range 

 

35 - 70Hz 

Pull in / drop out diff. frequency 

±9Hz 

Operating temperature 

 

-20°C to +70°C 

EMC 

 

 

CE according to EN50081-1, EN50082-1,  

 

 

 

EN50081-2, EN50082-2 

Approvals 

 

 

Certified by major classification societies 

Burn-in 

 

 

50 hours before final test 

Enclosure material 

 

Flame retardant 

Weight 

 

 

0.7kg 

Dimensions   

 

96 x 96 x 80mm (H x W x D) 

Panel cut out  

 

92 x 92mm (H x W) 

Check sync. relay 

Voltage difference 

 

10 - 20% 

Frequency difference 

 

0.15 - 0.3Hz          Combined setting 

Phase difference 

 

6 - 12° 

Dead bus delay 

 

1s – 5s 

Dead bus voltage offset 

 

20% - 40% 

Min. generator voltage for DB closure  80% of nominal voltage 

Contact rating 

 

AC: 250V, 1.2A, 125VA 

 

 

 

DC: 30V, 1A, 30W 

The specifications are subject to change without notice. 

 

Содержание M8100.0060

Страница 1: ...M8196 72E Page 1 of 7 M8100 Synchroscope User Manual SELCO Betonvej 11 DK 4000 Roskilde Denmark Phone 45 7026 1122 Fax 45 7026 2522 e mail selco selco com Web site www selco com...

Страница 2: ...2 of 7 Table of contents 1 Preface 3 2 Function 3 3 Connections 3 4 Adjustments 4 4 1 Check synchronizer relay 4 4 2 Dead bus closure 5 4 2 1 Voltage Offset 5 4 2 2 Dead busbar delay time 5 5 Specific...

Страница 3: ...on the rear side of the unit For clearing of blackout situations the M8100 Synchroscope can be set up to connect a live generator to a dead busbar dead busbar closure function When enabled the M8100 S...

Страница 4: ...busbar voltage are within limits for automatic closure or a pulse signal of 0 4 or 0 8s S1 pin1 OFF pulse signal S1 pin1 ON constant signal In case S1 pin1 is in OFF position S1 pin2 can be used for...

Страница 5: ...is to give room for possible noise on the busbar voltage input of M8100 Synchroscope The M8100 Synchroscope considers the busbar to be dead in case the busbar voltage is below the dead busbar voltage...

Страница 6: ...classification societies Burn in 50 hours before final test Enclosure material Flame retardant Weight 0 7kg Dimensions 96 x 96 x 80mm H x W x D Panel cut out 92 x 92mm H x W Check sync relay Voltage...

Страница 7: ...erminals 1 3 2 3 Type 4 6 5 6 Function M8100 0050 450V 400V With check synchronizer relay M8100 0060 230V With check synchronizer relay M8100 0070 480V 415V With check synchronizer relay M8100 0080 11...

Отзывы: