The highest tolerance is adjusted by turning the potentiometer P1 clockwise until end position. 
Then the limits are as follows: 

∆U = 20% 
∆f = 0,3Hz 
∆φ = 12

 

 

4.2

 

Dead bus closure 

This function enables the built-in check synchronizer relay to close the circuit breaker even though 
there is no voltage on the busbar. The generator voltage must be at least at 80% of the nominal 
voltage before the dead bus closure can activate. 

For activating the dead bus closure, terminals 9 and 10 must be bridged. 

4.2.1

 

Voltage Offset 

The purpose of the dead busbar voltage offset is to give room for possible noise on the busbar 
voltage input of M8100 Synchroscope.  

The M8100 Synchroscope considers the busbar to be dead in case the busbar voltage is below the 
dead busbar voltage offset. This offset can be adjusted by potentiometer P2. The range is between 
20% of nominal voltage to 40% of nominal voltage.  

Turning P2 counter clockwise until end position means 20%.  

Turning P2 clockwise until end position means 40%. 

4.2.2

 

Dead busbar delay time 

The dead bus closure facility will only close the breaker to the dead busbar in case the busbar 
voltage has been below the voltage offset limit during the entire time delay. This time delay can be 
adjusted by potentiometer P3. 

Turning P3 counter clockwise to end position: delay = 1s 

Turning P3 clockwise to end position: delay = 5s 

 

 

Содержание M8100.0060

Страница 1: ...M8196 72E Page 1 of 7 M8100 Synchroscope User Manual SELCO Betonvej 11 DK 4000 Roskilde Denmark Phone 45 7026 1122 Fax 45 7026 2522 e mail selco selco com Web site www selco com...

Страница 2: ...2 of 7 Table of contents 1 Preface 3 2 Function 3 3 Connections 3 4 Adjustments 4 4 1 Check synchronizer relay 4 4 2 Dead bus closure 5 4 2 1 Voltage Offset 5 4 2 2 Dead busbar delay time 5 5 Specific...

Страница 3: ...on the rear side of the unit For clearing of blackout situations the M8100 Synchroscope can be set up to connect a live generator to a dead busbar dead busbar closure function When enabled the M8100 S...

Страница 4: ...busbar voltage are within limits for automatic closure or a pulse signal of 0 4 or 0 8s S1 pin1 OFF pulse signal S1 pin1 ON constant signal In case S1 pin1 is in OFF position S1 pin2 can be used for...

Страница 5: ...is to give room for possible noise on the busbar voltage input of M8100 Synchroscope The M8100 Synchroscope considers the busbar to be dead in case the busbar voltage is below the dead busbar voltage...

Страница 6: ...classification societies Burn in 50 hours before final test Enclosure material Flame retardant Weight 0 7kg Dimensions 96 x 96 x 80mm H x W x D Panel cut out 92 x 92mm H x W Check sync relay Voltage...

Страница 7: ...erminals 1 3 2 3 Type 4 6 5 6 Function M8100 0050 450V 400V With check synchronizer relay M8100 0060 230V With check synchronizer relay M8100 0070 480V 415V With check synchronizer relay M8100 0080 11...

Отзывы: