SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System
Appendix B: Two-Branch Application
With these settings, Branch B operates using a fuse-blowing scheme where the
fuse clears faults on the branch, while Branch A operates separately, tripping
much faster because the protection does not wait for a fuse-coordination delay.
The required modifications for the SEL-651R Protection settings are not included
in this instruction manual. See SEL application guide
Using the SEL-FT50/
SEL-FR12 System to Selectively Permit Accelerated Tripping in the SEL-651R
Recloser
(AG2017-30), available at selinc.com.
Table 17
Settings for the SEL-FR12
Network ID
BAUD
RX_ADD
TX_ADD
Trio 1 Gain
Trio 2 Gain
Trio 3 Gain
Trio 4 Gain
3—(0010)
38400
1
2
High Gain
High Gain
High Gain
High Gain
Table 18
SEL-651R Settings
PROTO
SPEED
TXID
RXID
MB8A or MB8B
38400
1
2
Table 19
SEL-651R Transmit M
IRRORED
B
ITS
Settings
TMB1A
TMB2A
TMB3A
TMB4A
TMB5A
TMB6A
TMB7A
TMB8A
Comments
0
0
0
0
0
0
0
TRGTR
The
TARGET RESET
pushbutton of the
SEL-651R resets the latched
FAULT
LEDs of the SEL-FR12.