29
Date Code 20210405
Instruction Manual
SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System
Device Installation
The Trio 1 LINK, Trio 2 LINK, Trio 3 LINK, and Trip 4 LINK bit logic ignores
SEL-FT50 Fault Transmitters that have not been installed or detected. For exam-
ple, if SEL-FT50 Fault Transmitters with Unit IDs 4 and 5 are installed, but there
is no Unit ID 6, LINK 6 never asserts. The equation for the Trio 2 LINK is
reduced to LINK 4 AND LINK 5.
Table 8
Definition of FAULT and LINK Bits
Bit Label
Definition
LINK
u
u
= Unit ID 1–12
SEL-FR12 is receiving messages from SEL-FT50 Fault Transmitters.
Asserts whenever SEL-FR12
LINK
LED
u
is solidly illuminated.
Trio 1 LINK
Logical AND of the link status from the installed SEL-FT50 Fault Transmit-
ters with Unit IDs 1, 2, and 3
Trio 2 LINK
Logical AND of the link status from the installed SEL-FT50 Fault Transmit-
ters with Unit IDs 4, 5, and 6
Trio 3 LINK
Logical AND of the link status from the installed SEL-FT50 Fault Transmit-
ters with Unit IDs 7, 8, and 9
Trio 4 LINK
Logical AND of the link status from the installed SEL-FT50 Fault Transmit-
ters with Unit IDs 10, 11, and 12
FAULT
u
u
= Unit ID 1–12
Asserts for at least 116 ms when the SEL-FR12 receives a fault message from
the SEL-FT50 and deasserts thereafter; this bit is not latched (this differs
from the SEL-FR12
FAULT
LEDs, which are latched until reset).
Trio 1 FAULT Logical OR of the fault state from Unit IDs 1, 2, and 3
Trio 2 FAULT Logical OR of the fault state from Unit IDs 4, 5, and 6
Trio 3 FAULT Logical OR of the fault state from Unit IDs 7, 8, and 9
Trio 4 FAULT Logical OR of the fault state from Unit IDs 10, 11, and 12
Table 9
Detailed Command Set 2—SEL-FR12 M
IRRORED
B
ITS
Data Message Contents
Required SEL-651R Transmit M
IRRORED
B
ITS
(SEL
OGIC
Equations) for Detailed Command Set (2)
TMB1
TMB2
TMB3
TMB4
TMB5
TMB6
TMB7
TMB8
0
0
1
0
0
0
Clear link state
in SEL-FR12
Target reset on
SEL-FR12
HMI
SEL-651R Received M
IRRORED
B
ITS
(Relay Word bits)
RMB1
RMB2
RMB3
RMB4
RMB5
RMB6
RMB7
RMB8
Response During Normal Conditions (No Fault on Trio 1 or Trio 2)
Trio 1
FAULT = 0
Trio 2
FAULT = 0
LINK 1
LINK 2
LINK 3
LINK 4
LINK 5
LINK 6
Response During FAULT Indication (One or Both Trio 1 FAULT, Trio 2 FAULT Asserted)
Trio 1 FAULT
Trio 2 FAULT
FAULT 1
FAULT 2
FAULT 3
FAULT 4
FAULT 5
FAULT 6
Table 10
Detailed Command Set 3—SSEL-FR12 M
IRRORED
B
ITS
Data Message Contents (Sheet 1 of 2)
Required SEL-651R Transmit M
IRRORED
B
ITS
(SEL
OGIC
Equations) for Detailed Command Set (2)
TMB1
TMB2
TMB3
TMB4
TMB5
TMB6
TMB7
TMB8
0
0
1
1
0
0
Clear link state
in SEL-FR12
Target reset on
SEL-FR12
HMI