SEL-735 Quick-Start Guide

Date Code 20131015

AC

SEL

ERATOR

 QuickSet SEL-5030 Software

E. Commonly Used Configuration Settings

This section outlines commonly used meter configuration settings, including: Meter and Terminal Identifier, 
Current and Potential Transformer Ratios, Demand Metering, KYZ Pulse, Daylight Savings Time, Load 
Profile, Front-Panel Display, and Communications.

1. General Settings

The General settings include the Meter Identifier (MID), Terminal Identifier (TID), and Current and 
Potential Transformer Ratios (CTR and PTR).

To access General settings, expand 

General > Identifier and Scaling 

from the 

AC

SEL

ERATOR

 QuickSet 

settings editor tree.

a. MID and TID Settings

Meter reports include the MID and 
TID for easy meter identification. 
These configuration settings help 
uniquely identify each meter within 
a system.

Figure 11

MID, TID, CTR, and PTR Settings

b. Current and Potential Transformer 

Ratios

You can configure the meter to scale 
the following reports to report in 
primary units:

– Meter Reports (MET)

– Human Machine Interface (HMI)

– Load Profile (LDP)

– Display Points (DP)

– Distributed Network Protocol (DNP)

– Modbus

®

– CTR and PTR settings

– Front-Panel LCD

SEL

OGIC®

 control equations are secondary 

quantities and are unaffected by CTR and PTR values.

To set the CT and PT ratios, choose 

General > Identifier and Scaling

 from the 

AC

SEL

ERATOR

 

QuickSet settings editor tree. Note that the CTR and PTR values are net ratios. For example, a 1200:5 CT 
ratio equates to a CTR setting of 240.

Figure 12

Demand Metering

2. Demand Metering

The SEL-735 supports Thermal, Rolling, and 
Block demand types with intervals of 1, 5, 10, 15, 
30, and 60 minutes.

To configure demand metering, choose 

Metering 

> Demand

 from the 

AC

SEL

ERATOR

 QuickSet 

settings editor tree.

Quick Tip:

The MID setting must match the MV-90

®

 Master File 

Device ID setting.

Содержание sel-735

Страница 1: ...is section outlines essential installation information including front panel layout rear panel layout labels and dimensions A Front Panel Layout The front panel interface consists of programmable push...

Страница 2: ...Va Vb Vc Vn Ground Terminal I O Board Expansion Slot 2 4 Digital Inputs 4 Digital Outputs solid state or electromechanical or 4 Analog Outputs 4 Digital Solid State Outputs 7 36 in 187 0 mm 5 47 in 13...

Страница 3: ...ect auxiliary power supply input voltages to terminals A01 and A02 The SEL 735 supports three power supply options High voltage ac dc supply 85 275 Vdc 85 264 Vac Medium voltage dc only supply 19 58 V...

Страница 4: ...C B A Form 5 3 wire delta connection Voltages Wire the phase to phase voltages to terminals Z07 and Z09 Connect the neutral wire to terminals Z08 and Z10 Currents Wire the currents to terminals Z01 Z...

Страница 5: ...supports various optical probes Table 1 lists compatible probes and any special requirements A Overview SEL ships all SEL 735 meters with ACSELERATOR QuickSet Use ACSELERATOR QuickSet to perform the f...

Страница 6: ...ters in ACSELERATOR QuickSet select Communications Parameters Figure 4 shows the default serial port parameters for the SEL 735 Figure 4 Default Communications Parameters Figure 5 SEL 735 Serial Port...

Страница 7: ...iguration settings at the bottom of the screen Right click on any setting for the previous or default value Figure 8 Meter Configuration Settings Figure 9 Save Settings 4 Save Configuration Settings t...

Страница 8: ...r within a system Figure 11 MID TID CTR and PTR Settings b Current and Potential Transformer Ratios You can configure the meter to scale the following reports to report in primary units Meter Reports...

Страница 9: ...in just 30 hours EXAMPLE 1 Map a Form A KY Pulse Setting to OUT401 Step 1 Select Inputs Outputs KYZ Pulse Outputs from the ACSELERATOR QuickSet settings editor tree Step 2 Set KE1_OUT to OUT401 ACSEL...

Страница 10: ...eter ships with the 2007 United States DST calendar The meter begins DST on the second Sunday in March at 2 00 a m and ends DST on the first Sunday in November at 2 00 a m To enable DST choose Dayligh...

Страница 11: ...rty meter reading software such as MV 90 from Itron can automatically read LDP data from the SEL 735 The data are also available through the SEL Ymodem Modbus and DNP protocols Figure 17 Load Profile...

Страница 12: ...tor tree Table 2 Available Communications Protocols Protocols Ethernet Port 1a a Additional cost option Serial EIA 485 Modem and EIA 232 Port 2 Port 3 Port 4a Front Port Port F SEL ASCII MODM Modbus R...

Страница 13: ...e VB VC and IB IC connections are swapped The system responds with unexpected ACB phase rotation instead of the IEEE standard ABC rotation The SEL 735 still registers energy correctly but the power qu...

Страница 14: ...with the actual front optical port Click Exit Test Mode at the end of an accuracy test to restore normal meter operation Figure 24 Test Mode E Control Window The control window provides an interface t...

Страница 15: ...use it is a six character word found in the dictionary The password O h pVw is strong because it is random undefined and contains eight characters Step 1 Access ACSELERATOR QuickSet HMI as previously...

Страница 16: ...ederal and international copyright and patent laws in its products including without lim itation software firmware and documentation The information in this document is provided for informational use...

Отзывы: