Sel sel-735 Скачать руководство пользователя страница 1

Date Code 20131015

SEL-735 Quick-Start Guide

Quick-Start Guide

I.

Introduction

This 

Quick-Start Guide

 explains how to 

install, configure, test, and operate the 
SEL-735 Power Quality and Revenue 
Meter. For detailed information on these 
topics, please refer to the 

SEL-735 Power 

Quality and Revenue Meter Instruction 
Manual

 located at 

www.selinc.com

.

II. SEL-735 Overview

This section outlines essential installation information, including front-panel layout, rear-panel layout, labels, and 
dimensions.

A. Front-Panel Layout

The front-panel interface consists of programmable pushbuttons and LEDs, an LCD, a keypad, a test mode LED, 
and an optical communications port.

Figure 1

Front-Panel Layout

Optical port, 
communications 
and test mode LED

Programmable 
local-control button

Potential LEDs

Programmable LEDs

Programmable LCD

Programmable 
control 
pushbuttons

Enable LED

TEST LED

Menu pushbuttons 
for settings

SEL-735 Power Quality and Revenue Meter

Содержание sel-735

Страница 1: ...is section outlines essential installation information including front panel layout rear panel layout labels and dimensions A Front Panel Layout The front panel interface consists of programmable push...

Страница 2: ...Va Vb Vc Vn Ground Terminal I O Board Expansion Slot 2 4 Digital Inputs 4 Digital Outputs solid state or electromechanical or 4 Analog Outputs 4 Digital Solid State Outputs 7 36 in 187 0 mm 5 47 in 13...

Страница 3: ...ect auxiliary power supply input voltages to terminals A01 and A02 The SEL 735 supports three power supply options High voltage ac dc supply 85 275 Vdc 85 264 Vac Medium voltage dc only supply 19 58 V...

Страница 4: ...C B A Form 5 3 wire delta connection Voltages Wire the phase to phase voltages to terminals Z07 and Z09 Connect the neutral wire to terminals Z08 and Z10 Currents Wire the currents to terminals Z01 Z...

Страница 5: ...supports various optical probes Table 1 lists compatible probes and any special requirements A Overview SEL ships all SEL 735 meters with ACSELERATOR QuickSet Use ACSELERATOR QuickSet to perform the f...

Страница 6: ...ters in ACSELERATOR QuickSet select Communications Parameters Figure 4 shows the default serial port parameters for the SEL 735 Figure 4 Default Communications Parameters Figure 5 SEL 735 Serial Port...

Страница 7: ...iguration settings at the bottom of the screen Right click on any setting for the previous or default value Figure 8 Meter Configuration Settings Figure 9 Save Settings 4 Save Configuration Settings t...

Страница 8: ...r within a system Figure 11 MID TID CTR and PTR Settings b Current and Potential Transformer Ratios You can configure the meter to scale the following reports to report in primary units Meter Reports...

Страница 9: ...in just 30 hours EXAMPLE 1 Map a Form A KY Pulse Setting to OUT401 Step 1 Select Inputs Outputs KYZ Pulse Outputs from the ACSELERATOR QuickSet settings editor tree Step 2 Set KE1_OUT to OUT401 ACSEL...

Страница 10: ...eter ships with the 2007 United States DST calendar The meter begins DST on the second Sunday in March at 2 00 a m and ends DST on the first Sunday in November at 2 00 a m To enable DST choose Dayligh...

Страница 11: ...rty meter reading software such as MV 90 from Itron can automatically read LDP data from the SEL 735 The data are also available through the SEL Ymodem Modbus and DNP protocols Figure 17 Load Profile...

Страница 12: ...tor tree Table 2 Available Communications Protocols Protocols Ethernet Port 1a a Additional cost option Serial EIA 485 Modem and EIA 232 Port 2 Port 3 Port 4a Front Port Port F SEL ASCII MODM Modbus R...

Страница 13: ...e VB VC and IB IC connections are swapped The system responds with unexpected ACB phase rotation instead of the IEEE standard ABC rotation The SEL 735 still registers energy correctly but the power qu...

Страница 14: ...with the actual front optical port Click Exit Test Mode at the end of an accuracy test to restore normal meter operation Figure 24 Test Mode E Control Window The control window provides an interface t...

Страница 15: ...use it is a six character word found in the dictionary The password O h pVw is strong because it is random undefined and contains eight characters Step 1 Access ACSELERATOR QuickSet HMI as previously...

Страница 16: ...ederal and international copyright and patent laws in its products including without lim itation software firmware and documentation The information in this document is provided for informational use...