background image

SEL Application Guide 2000-02 

 

Date Code 20070803 

Protocol 

Selection 

     (Continued 

from 

previous 

page) 

PROTO   := MBA 
Communications Settings 
MBT     := N        SPEED   := 38400    STOPBIT := 2 
 
Mirrored Bits Protocol Setting 

TX_ID   := 2        RX_ID   := 1        RBADPU  := 10       CBADPU  := 20000 
TXMODE  := P        MBNUM   := 8        RMB1FL  := P        RMB1PU  := 1 
RMB1DO  := 1        RMB2FL  := P        RMB2PU  := 1        RMB2DO  := 1 
RMB3FL  := P        RMB3PU  := 1        RMB3DO  := 1        RMB4FL  := P 
RMB4PU  := 1        RMB4DO  := 1        RMB5FL  := P        RMB5PU  := 1 
RMB5DO  := 1        RMB6FL  := P        RMB6PU  := 1        RMB6DO  := 1 
RMB7FL  := P        RMB7PU  := 1        RMB7DO  := 1        RMB8FL  := P 
RMB8PU  := 1        RMB8DO  := 1 

Set PROTO equal to MB

x

, where 

equals A or B depending on which M

IRRORED 

B

ITS 

channel 

is being used. Set MBT equal to N to disable that option.  

Set SPEED equal to 38400.  

Set STOPBIT equal to 2.  

Set the RXID equal to one and TXID equal to two at the Master End. At the remote or Slave End, 
set the RXID equal to two and the TXID to one. The relays use these addresses so that the master 
relay only receives messages sent by a relay with the matching transmit address and vice versa.  

Set TXMODE equal to P (Paced). 

To connect the relay to the radio, use an SEL-C285 cable, DB-9 male to DB-9 male straight-
through.  If complete electrical isolation is desired between the radio and antenna and the relay’s 
EIA-232 communications port, use the SEL-2815M Fiber-Optic Transceivers and fiber-optic 
cable to connect the relay to the radio as shown in Figure 1. 

R

ADIO 

S

ETTINGS AND 

C

ONNECTIONS

 

The FGR-115MB has settings that require adjustment prior to installation.  Invoke the setup 
program by connecting the radio to any terminal emulator program, using the DB-9 
straight-through cable supplied with the radio.  Set the terminal baud rate to 19200, and put the 
radio in setup mode by pressing the Setup Button; when setup mode is invoked, all three LEDs on 
the radio turn green, and a menu is displayed on the terminal screen as shown below. 

                                MAIN MENU 
                         SEL Version 5.72 06-27-2001 
                           Standard Hop Table 
                        Modem Serial Number 897-0002 
 
(0)   Set Operation Mode 
(1)   Set Baud Rate 
(2)   Edit Call Book 
(3)   Edit Radio Transmission Characteristics 
(4)   Show Radio Statistics 
(5)   Edit MultiPoint Parameters 
(6)   TDMA Menu 
(Esc) Exit Setup 
 
Enter Choice 

Simply enter menu choices and selections to make the following settings enabled.  Start with the 
Set Operation mode (0). 

Содержание MIRRORED BITS FGR-115MB

Страница 1: ...tomated sectionalizing and load restoration bus protection and much more Freewave FGR 115MB Transceiver NO 1 slave SEL 351S 7 Relay RXID 1 TXID 2 SEL 351R Cabinet FreeWave FGR 115MB Transceiver NO 1 m...

Страница 2: ...to 10 miles based on an unobstructed line of sight SECURITY MIRRORED BITS repeatedly sends data in an encoded message Each of eight data bits is sent three times within each message Received messages...

Страница 3: ...P 2 Enter Port 2 PROTO MB8A SPEED 38400 RTSCTS N RBADPU 60 CBADPU 1000 RXID 1 TXID 2 RXDFLT XXXXXXXX RMB1PU 1 RMB1DO 1 RMB2PU 1 RMB2DO 1 RMB3PU 1 RMB3DO 1 RMB4PU 1 RMB4DO 1 RMB5PU 1 RMB5DO 1 RMB6PU 1...

Страница 4: ...elay to the radio use an SEL C285 cable DB 9 male to DB 9 male straight through If complete electrical isolation is desired between the radio and antenna and the relay s EIA 232 communications port us...

Страница 5: ...200 6 9 600 7 4 800 8 2 400 9 1 200 A Data Parity 0 B MODBus RTU 0 C RS232 485 0 D Setup Port 2 E TurnOffDelay 0 TurnOnDelay 0 E TurnOffDelay 0 F TurnOffDelay 0 Esc Exit to Main Menu Enter Choice The...

Страница 6: ...the area if known From the radio parameters menu enter 0 followed by an F to set the hop table size to 112 and the hop freq offset to zero RADIO PARAMETERS WARNING Do not change parameters without rea...

Страница 7: ...pment list details the required components and connections as shown in Figure 1 A pole tower or other means of elevating the antenna is not shown Table 1 Equipment List No Item Description Approx Cost...

Страница 8: ...eciate your interest in SEL products and services If you have questions or comments please contact us at Schweitzer Engineering Laboratories Inc 2350 NE Hopkins Court Pullman WA 99163 5603 USA Telepho...

Отзывы: