Sel AR360 Скачать руководство пользователя страница 2

                    

                    

                    

25-0081

Page 2 of 2

SCHWEITZER ENGINEERING LABORATORIES, INC.

2350 NE Hopkins Court • Pullman, WA 99163-5603  U.S.A.

Phone: +1.509.332.1890 • Fax: +1.509.332.7990

selinc.com • [email protected]

AR360

Installation Instructions

Install the Phase Sensor(s)

                    

Test Activation and Clearing

                    

Note: 

To remove the fault indicator from the conductor, use an insulated hot stick to grasp the indicator at the molded hookeye on 

the face of the indicator. Start pulling the AR360 off until you feel resistance between the spring clamp and the conductor. Then 
complete the removal process by applying a twisting motion to the hot stick.

                    

                    

                    

                    

                    

                    

                    

                    

CAUTION

Do not extend the spring 
beyond parallel with the 
housing, as shown. Over-
extension of the spring 
may cause a loss of 
clamping force.

                    

Use a hot stick to grasp the 
molded hookeye on the face of 
the phase sensor.

                    

Position the spring clamp 
against the conductor and 
retaining bar, as shown.

                    

Position the indicator with the 
conductor against the retaining 
bar and ensure that the indica-
tor is held in place by the 
spring clamp.

1. Remove the shorting bar from the CRSRTT.

2. Place the exposed magnet directly against the product number 

AR360

 on the label, holding the tool parallel to the label.

3. Hold the tool against the logo for 6 to 8 seconds.

4. Remove the CRSRTT tool. The AR360 will cycle the flash 

sequence to demonstrate its activation.

5. Replace the CRSRTT shorting bar for storage.

                    

Spring 
Clamp

Conductor

Retaining 
Bar

CRSRTT

Shorting
Bar

Flash Sequence:

• Red and yellow LEDs

repeat the permanent fault
sequence for 40 seconds.

• Yellow LEDs repeat

single-flash sequences for 
20 seconds.

• The unit turns off 

automatically.